| Plan Review Notes For Permit 08020529 |
| Permit Number |
08020529 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-26 13:21:21 | DENIED; | | | 1. WATER HEATER DETAILS; SHOW TYPE OF THERMAL EXPANION | | | TO BE USED PER FBC PLUMBING SECTION 607.3. IF A HEATER | | | PAN IS USED ON FIRST FLOOR PAN DRAIN IS REQUIRED AND | | | MUST GO TO OUT SIDE SECTION 504.7.2. | | | 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3" TO | | | SANITARY TEE SECTION 406.3. | | | 3. WATER RISER DIAGRAM; ONLY ON WATER HEATER SHOWN. T & | | | P DISCHARGE PIPE TO BE 3/4"( ON HEATER SHOWN.) SHOCK | | | ARRESTORS ARE NOT REQUIRED ON ALL FIXTURES SEE SECTION | | | 604.9 | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|