| 2008-02-26 08:37:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO MECHANICAL |
| | PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10). |
| | |
| | 3) SEE AIR HANDLER #1 RETURN AIR THROUGH 20X20 GRILL IN |
| | DOOR, IF THE POCKET DOOR AT THE SERVICE HALL AND MAIN |
| | HALL IS CLOSED THAN AIR CAN NOT RETURN TO THE AIR |
| | HANDLER, PLEASE CORRECT, PER 2004 FBC/R M1602.4. |
| | |
| | 4) PLEASE CLARIFY ON PLAN HOW AIR IS TO RETURN TO AIR |
| | HANDLER #1, SEE 2004 FBC/R M1602.4. |
| | |
| | 5) SEE AIR HANDLER #3 RETURN AIR DUCTS FROM BEDROOMS IS |
| | NOT CONNECTED TO THE AIR HANDLER AND WILL NOT LET AIR |
| | RETURN TO THE AIR HANDLER, PLEASE CORRECT. |
| | |
| | 6) SEE AIR HANDLER #3 IF THE 20X20 RETURN AIR GRILL IS |
| | IN THE CLOSET AND THE DOOR IS CLOSED THEN AIR WILL NOT |
| | RETURN TO THE AIR HANDLER, PLEASE CORRECT. |
| | |
| | 6) SEE YELLOW HIGH LIGHT ON MECHANICAL PLANS A/C1 AND |
| | A/C2 SHOWING SUPPLY AIR DUCTS THAT NEED TO BE SIZED, |
| | PER 2004 WPB AMEND. 106.3.5.4 (10). |
| | |
| | ** PER 2004 FBC/R M1602.4BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN |
| | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE |
| | PROPER RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| | SHALL BE INCLUDED. |
| | |