Plan Review Notes
Plan Review Notes For Permit 08020529
Permit Number 08020529
Review Stop M
Sequence Number 1
Notes
Date Text
2008-02-26 08:37:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE ADD AN A/C EQUIPMENT SCHEDULE TO MECHANICAL
 PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 3) SEE AIR HANDLER #1 RETURN AIR THROUGH 20X20 GRILL IN
 DOOR, IF THE POCKET DOOR AT THE SERVICE HALL AND MAIN
 HALL IS CLOSED THAN AIR CAN NOT RETURN TO THE AIR
 HANDLER, PLEASE CORRECT, PER 2004 FBC/R M1602.4.
  
 4) PLEASE CLARIFY ON PLAN HOW AIR IS TO RETURN TO AIR
 HANDLER #1, SEE 2004 FBC/R M1602.4.
  
 5) SEE AIR HANDLER #3 RETURN AIR DUCTS FROM BEDROOMS IS
 NOT CONNECTED TO THE AIR HANDLER AND WILL NOT LET AIR
 RETURN TO THE AIR HANDLER, PLEASE CORRECT.
  
 6) SEE AIR HANDLER #3 IF THE 20X20 RETURN AIR GRILL IS
 IN THE CLOSET AND THE DOOR IS CLOSED THEN AIR WILL NOT
 RETURN TO THE AIR HANDLER, PLEASE CORRECT.
  
 6) SEE YELLOW HIGH LIGHT ON MECHANICAL PLANS A/C1 AND
 A/C2 SHOWING SUPPLY AIR DUCTS THAT NEED TO BE SIZED,
 PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 ** PER 2004 FBC/R M1602.4BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]