| Date |
Text |
| 2008-02-25 14:29:00 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NECK, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1}THE ELECTRICAL CALCULATIONS ON SHEET E1 INDICATE A |
| | 200 AMP SERVICE WITH CONDUCTORS FOR THAT SIZE, SHEET E2 |
| | INDICATES A 400 AMP SERVICE , SEE RISER DIAGRAM, |
| | CORRELATE SAME. |
| | |
| | 2}LOCATE THE SERVICE EQUIPMENT, METER GUTTER AND MAIN |
| | DISCONNECT ON THE PLAN SO THAT COMPLIANCE WITH ARTICLES |
| | 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} 250.122(F)(1) BASED ON RATING OF OVERCURRENT |
| | PROTECTIVE DEVICE EACH PARALLEL EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE SIZED ON THE BASIS OF THE AMPERE |
| | RATING OF THE OVERCURRENT DEVICE PROTECTING THE CIRCUIT |
| | CONDUCTORS IN THE RACEWAY OR CABLE IN ACCORDANCE WITH |
| | TABLE 250.122.SEE TABLE, THE #4 IN THE RISER DIAGRAM |
| | DOES NOT COMPLY. |
| | |
| | 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 5} THE SERVICE GROUNDING ELECTRODE SYSTEM MUST BE RAN |
| | TO FOOTER STEEL TO COMPLY WITH 250.52(A)(3).INDICATE |
| | SAME ON RISER AND NOTES IN THE ELECTRICAL CALCULATION |
| | |
| | 6} THERE IS NO "FIRST 10000VA" REDUCTION FOR |
| | CALCULATING THE NEUTRAL LOAD. SEE 220.61 AND ANNEX "D", |
| | PAGE 718, 2005 NEC. |
| | |
| | 7} PANEL SCHEDULE "A, CIRCUITS #4 FOR THE FREEZER AND |
| | #6 WINE COOLER, THESE APPLIANCES WERE NOT IN THE LOAD |
| | CALCULATION.220.14(A). |
| | |
| | 8} THE ELEVATOR IS NOT LISTED IN EITHER PANEL SEE 408.4 |
| | 2005 NEC. |
| | |
| | 9} THE WHIRLPOOL CIRCUIT IS NOT LISTED IN THE PANEL |
| | SCHEDULE. SEE 680.56 FOR GFCI PROTECTION. |
| | |
| | 10} THE KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 11} THE EXERCISE ROOM, BREAKFAST ROOM AND THE OFFICE |
| | MUST COMPLY WITH THE SPACING REQUIREMENTS OF |
| | 210.52(A)(1) AND (2).SEE REVIEWED PLAN FOR |
| | DEFICIENCIES. |
| | |
| | 12} THE LOCATION OF THE DISCONNECTS FOR THE AIR |
| | HANDLERS #1 & #2 DO NOT COMPLY WITH THE CLEARANCE |
| | REQUIREMENTS OF 110.26. |
| | |
| | 13} THE BRANCH CIRCUITS REQUIRED BY 620.23(A), (B) AND |
| | (C) ARE NOT LISTED ON THE PANEL SCHEDULE. 408.4.NEC. |
| | |
| | 14} THE ELEVATOR DISCONNECT IN THE ATTIC DOES NOT |
| | COMPLY WITH 110.26 OR 620.51(C). IT CAN BE LOCATED IN |
| | THE MECHANICAL ROOM. |
| | |
| | 15} A NOTE ON SHEET E2 INDICATES THE A/C IS IN THE |
| | ATTIC, BUT SHOWN IN A CLOSET ALSO SAME LOCATION ON THE |
| | MECHANICAL PLAN, CORRELATE LOCATION. |
| | |
| | 16} BEDROOMS 2 & 3 SHEET E2 RECEPTACLE SPACING MUST |
| | COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005 NEC. |
| | SEE REVIEWED PLAN FOR DEFICIENCIES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |