Plan Review Notes
Plan Review Notes For Permit 08020529
Permit Number 08020529
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-25 14:29:00 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NECK, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1}THE ELECTRICAL CALCULATIONS ON SHEET E1 INDICATE A
 200 AMP SERVICE WITH CONDUCTORS FOR THAT SIZE, SHEET E2
 INDICATES A 400 AMP SERVICE , SEE RISER DIAGRAM,
 CORRELATE SAME.
  
 2}LOCATE THE SERVICE EQUIPMENT, METER GUTTER AND MAIN
 DISCONNECT ON THE PLAN SO THAT COMPLIANCE WITH ARTICLES
 225 AND 230 CAN BE REVIEWED.
  
 3} 250.122(F)(1) BASED ON RATING OF OVERCURRENT
 PROTECTIVE DEVICE EACH PARALLEL EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED ON THE BASIS OF THE AMPERE
 RATING OF THE OVERCURRENT DEVICE PROTECTING THE CIRCUIT
 CONDUCTORS IN THE RACEWAY OR CABLE IN ACCORDANCE WITH
 TABLE 250.122.SEE TABLE, THE #4 IN THE RISER DIAGRAM
 DOES NOT COMPLY.
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 5} THE SERVICE GROUNDING ELECTRODE SYSTEM MUST BE RAN
 TO FOOTER STEEL TO COMPLY WITH 250.52(A)(3).INDICATE
 SAME ON RISER AND NOTES IN THE ELECTRICAL CALCULATION
  
 6} THERE IS NO "FIRST 10000VA" REDUCTION FOR
 CALCULATING THE NEUTRAL LOAD. SEE 220.61 AND ANNEX "D",
 PAGE 718, 2005 NEC.
  
 7} PANEL SCHEDULE "A, CIRCUITS #4 FOR THE FREEZER AND
 #6 WINE COOLER, THESE APPLIANCES WERE NOT IN THE LOAD
 CALCULATION.220.14(A).
  
 8} THE ELEVATOR IS NOT LISTED IN EITHER PANEL SEE 408.4
 2005 NEC.
  
 9} THE WHIRLPOOL CIRCUIT IS NOT LISTED IN THE PANEL
 SCHEDULE. SEE 680.56 FOR GFCI PROTECTION.
  
 10} THE KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 11} THE EXERCISE ROOM, BREAKFAST ROOM AND THE OFFICE
 MUST COMPLY WITH THE SPACING REQUIREMENTS OF
 210.52(A)(1) AND (2).SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 12} THE LOCATION OF THE DISCONNECTS FOR THE AIR
 HANDLERS #1 & #2 DO NOT COMPLY WITH THE CLEARANCE
 REQUIREMENTS OF 110.26.
  
 13} THE BRANCH CIRCUITS REQUIRED BY 620.23(A), (B) AND
 (C) ARE NOT LISTED ON THE PANEL SCHEDULE. 408.4.NEC.
  
 14} THE ELEVATOR DISCONNECT IN THE ATTIC DOES NOT
 COMPLY WITH 110.26 OR 620.51(C). IT CAN BE LOCATED IN
 THE MECHANICAL ROOM.
  
 15} A NOTE ON SHEET E2 INDICATES THE A/C IS IN THE
 ATTIC, BUT SHOWN IN A CLOSET ALSO SAME LOCATION ON THE
 MECHANICAL PLAN, CORRELATE LOCATION.
  
 16} BEDROOMS 2 & 3 SHEET E2 RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A)(1) AND 210.52(A)(2). 2005 NEC.
 SEE REVIEWED PLAN FOR DEFICIENCIES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718