| 2008-03-06 15:21:57 | |
| | |
| | DENIED |
| | |
| | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $1,047.92 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. ALSO NO WALL TYPE AND R-VALUE WAS GIVEN |
| | FOR THE 2ND FLOOR EXTERIOR WOOD FRAME WALLS AT THE |
| | MASTER BEDROOM BALCONY AREA |
| | |
| | 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN |
| | BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN |
| | AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED |
| | |
| | 7)NO PRODUCT APPROVALS WERE SUBMITTED FOR GLASS |
| | BLOCK, MULLIONS, LINTELS, AND CONNECTORS AND STRAPS. IN |
| | LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE |
| | LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE WITH THE |
| | STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON |
| | TIE?S COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED |
| | HIGHLIGHTED |
| | |
| | 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH |
| | R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE |
| | INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD |
| | |
| | 9)PLEASE NOTE THAT MORTAR JOINED GLASS BLOCK ONLY |
| | MEETS THE REQUIREMENT OF SMALL MISSILE IMPACT AND NOT |
| | LARGE MISSILE AS REQUIRED WHEN OPENINGS ARE WITHIN 30 |
| | FEET OF GRADE |
| | |
| | 10)DOES THE FIXED WINDOW PRODUCT APPROVAL COVER THE |
| | HALF CIRCLE ABOVE THE SINGLE HUNG UNITS AND THE FULL |
| | ROUND WINDOW AS THERE IS NO INFORMATION IN NOA |
| | |
| | 11)THE NOA FOR THE ROOF TILES HAS EXPIRED, IT HAS |
| | BEEN RENEWED UNDER MIAMI-DADE NOA #07-0914.13 |
| | |
| | 12)PROVIDE INFORMATION THAT SHOWS BEDROOM 2 AND 3 |
| | WINDOWS WILL MEET EGRESS REQUIREMENTS, MASTER BEDROOM |
| | DOES NOT REQUIRE EGRESS WINDOW AS DOORS ARE PROVIDED, |
| | ALSO NOTE THAT WINDOW SCHEDULE SHOWS DIFFERENT SIZES |
| | FOR THESE WINDOWS BUT ELEVATION SHOWS THEM AS IDENTICAL |
| | IN SIZE |
| | |
| | 13)SECTION 2 ON SHEET S-3DOES NOT CORRESPOND WITH |
| | THE DESIGNATION FROM S-2, TRUSS JOISTS RUN |
| | PERPENDICULAR TO THE BEAM, ALSO BEAM IS SHOWNAS TYPE |
| | B2 ON PLAN AND TYPE B4 ON SECTION |
| | |
| | 14)SECTION 3 ON S-3 SHOWS BEAM AS TYPE B4 AND THE |
| | PLAN ON S-2 SHOWS IT AS TYPE B5 |
| | |
| | 15)PROVIDE A DETAIL FOR REINFORCING STEEL LAYOUT IN |
| | ARCHED TIE BEAMS |
| | |
| | 16)CORRECT NOTE #1 IN THE BEAM NOTES ON SHEET S-3 FOR |
| | ON CENTER SPACING |
| | |
| | 17)CORRECT CHIMNEY CRICKET AND ROOF SHEATHING TO MEET |
| | THE REQUIREMENTS OF R1001.17 FBC RES. AND FIRE BLOCK |
| | GIRDER TRUSS AT CHIMNEY PER R1001.16 FBC RES. ON SHEET |
| | A-7 SECTION 3 |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006 |
| | AMENDMENTS |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | FBC RES. = FLORIDA BUILDING CODE |
| | RESIDENTIAL 2004 W/2006 AMENDMENTS |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |