Plan Review Notes
Plan Review Notes For Permit 08020529
Permit Number 08020529
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-06 15:21:57 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $1,047.92 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL. ALSO NO WALL TYPE AND R-VALUE WAS GIVEN
 FOR THE 2ND FLOOR EXTERIOR WOOD FRAME WALLS AT THE
 MASTER BEDROOM BALCONY AREA
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN
 BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 7)NO PRODUCT APPROVALS WERE SUBMITTED FOR GLASS
 BLOCK, MULLIONS, LINTELS, AND CONNECTORS AND STRAPS. IN
 LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE
 LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE WITH THE
 STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON
 TIE?S COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED
  
 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 9)PLEASE NOTE THAT MORTAR JOINED GLASS BLOCK ONLY
 MEETS THE REQUIREMENT OF SMALL MISSILE IMPACT AND NOT
 LARGE MISSILE AS REQUIRED WHEN OPENINGS ARE WITHIN 30
 FEET OF GRADE
  
 10)DOES THE FIXED WINDOW PRODUCT APPROVAL COVER THE
 HALF CIRCLE ABOVE THE SINGLE HUNG UNITS AND THE FULL
 ROUND WINDOW AS THERE IS NO INFORMATION IN NOA
  
 11)THE NOA FOR THE ROOF TILES HAS EXPIRED, IT HAS
 BEEN RENEWED UNDER MIAMI-DADE NOA #07-0914.13
  
 12)PROVIDE INFORMATION THAT SHOWS BEDROOM 2 AND 3
 WINDOWS WILL MEET EGRESS REQUIREMENTS, MASTER BEDROOM
 DOES NOT REQUIRE EGRESS WINDOW AS DOORS ARE PROVIDED,
 ALSO NOTE THAT WINDOW SCHEDULE SHOWS DIFFERENT SIZES
 FOR THESE WINDOWS BUT ELEVATION SHOWS THEM AS IDENTICAL
 IN SIZE
  
 13)SECTION 2 ON SHEET S-3DOES NOT CORRESPOND WITH
 THE DESIGNATION FROM S-2, TRUSS JOISTS RUN
 PERPENDICULAR TO THE BEAM, ALSO BEAM IS SHOWNAS TYPE
 B2 ON PLAN AND TYPE B4 ON SECTION
  
 14)SECTION 3 ON S-3 SHOWS BEAM AS TYPE B4 AND THE
 PLAN ON S-2 SHOWS IT AS TYPE B5
  
 15)PROVIDE A DETAIL FOR REINFORCING STEEL LAYOUT IN
 ARCHED TIE BEAMS
  
 16)CORRECT NOTE #1 IN THE BEAM NOTES ON SHEET S-3 FOR
 ON CENTER SPACING
  
 17)CORRECT CHIMNEY CRICKET AND ROOF SHEATHING TO MEET
 THE REQUIREMENTS OF R1001.17 FBC RES. AND FIRE BLOCK
 GIRDER TRUSS AT CHIMNEY PER R1001.16 FBC RES. ON SHEET
 A-7 SECTION 3
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW