Plan Review Notes
Plan Review Notes For Permit 08020520
Permit Number 08020520
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-05 20:22:08** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SUBMIT PLANS/DETAILS FOR REQUIRED
 GROUNDING ELECTRODE SYSTEM FOR FOOTINGS PER 250.50
 PLEASE INCLUDE ON SHEETS CONTAINING TITLE BLOCKS,
 SIGNED, DATED AND SEALED BY THE ELECTRICAL DESIGNER OF
 RECORD FOR BASE BUILDING.
  
 2) NOTE: PLEASE SUBMIT DETAILS FOR ANY SLAB, UNDER
 GROUND CONDUITS, OR DUCT BANKS WHICH MAY BE GETTING
 INSTALLED IN FOOTINGS, SLAB ETC.
 FBC106.3.5.1.2, 106.1.2
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  