| 2008-03-08 20:26:57 | ** DENIED ** |
| | |
| | ** 400 S. AUSTRALIAN AVE. |
| | PERMIT #08020504 |
| | |
| | ** A PRELIMINARY REVIEW WAS DONE AND PROVIDED TO THE |
| | ENGINEER SEVERAL MONTHS AGO HOWEVER MOST OF THE SAME |
| | ITEMS GIVEN ON THAT REVIEW ARE STILL THE SAME ON |
| | PLANS. |
| | |
| | 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW |
| | ELECTRICAL HOWEVER THIS SCOPE OF WORK SHOULD HAVE BEEN |
| | INCLUDED WITH OTHER SCOPE OF WORK AS APPLIED UNDER |
| | OTHER PERMIT NUMBERS. |
| | AS SUBMITTED, EACH SET OF PLANS SUBMITTED UNDER EACH |
| | PERMIT WILL BE REQUIRED TO CONTAIN ALL OTHER |
| | INFORMATION FROM OTHER PERMITS. AS EACH IS A SEPARATE |
| | RECORD AND EACH HAS A DIRECT AFFECT ON THE OTHER |
| | COMPLETE SETS WILL BE REQUIRED FOR ALL PERMITS. |
| | PLEASE KNOW AS OF THIS REVIEW A NOTICE HAS BEEN SENT TO |
| | BUILDING OFFICIAL ON HOW THE PERMITS WERE APPLIED. |
| | PLEASE SEE REVIEWS UNDER OTHER APPLIED PERMITS. THESE |
| | MAY ALL BE COMING IN UNDER CONSOLIDATE PERMIT(S) BEFORE |
| | ALL REVIEWS ARE COMPLETED AND WITH RELEVANT SUB PERMITS |
| | NEEDED. |
| | PLANS AND ALL PERMIT APPLICATIONS AND DOCUMENTS AS |
| | SUBMITTED ARE VERY CONFUSING AS APPLIED EVEN THOUGH |
| | THIS REVIEWER UNDERSTANDS THE INTENT OF THE PROPOSED |
| | TOTAL SCOPE OF WORK. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE PLANS UNDER DESIGNS |
| | FOR: |
| | NFPA-70 2005 |
| | NFPA-20 2003 |
| | NFPA-110 2002 |
| | NFPA-101 2003 |
| | |
| | ** THERE ARE TOO MANY ITEMS TO LIST ALL CODE VIOLATIONS |
| | ON THIS LIST. THE FOLLOWING ARE SOME ITEMS. |
| | |
| | 3) NOTE: PLEASE SEE NFPA-20, THE FIRE PUMP DISCONNECT |
| | AND SERVICE EQUIPMENT SHALL NOT BE LOCATED IN THE MAIN |
| | ELECTRICAL ROOMS. |
| | PLEASE ALSO SUBMIT COMPLETE INFORMATION FOR FPC, FP, |
| | FOR LOCKED ROTOR OVER CURRENT PROTECTION ETC. |
| | PLEASE SEE NEC 695.3, 695.4 AND NFPA-20 CHAPTERS 9 AND |
| | 10. ETC |
| | THERE ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR |
| | CODE COMPLIANCE. |
| | |
| | 4) NOTE: PLEASE SEE 230.71, 230.70 AS NO MORE THAN 8FT |
| | OF UNPROTECTED CONDUCTORS SHALL BE PERMITTED INSIDE THE |
| | BUILDING. |
| | |
| | 5) NOTE: PLANS SHOWS THE REMOVAL OF THE UN-PERMITTED |
| | GENERATOR FOR CELL SITE HOWEVER PLANS DO NOT PROVIDE |
| | ENOUGH INFORMATION ON THIS UNIT. WILL THIS BE REMOVED |
| | AND RE-INSTALLED UNDER SEPARATE PERMIT, PLANS ETC? |
| | |
| | 6) NOTE: PLEASE KNOW AS THE SEPARATE PERMIT WAS SUBMIT |
| | FOR GENERATOR NOT ENOUGH INFORMATION FOR NEW LOADS ON |
| | PROPOSED |
| | ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER |
| | PERMIT APPLICATIONS FOR THIS SAME LOCATION, PLEASE SEE |
| | ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER |
| | REVIEWS. |
| | 700, 701, 702 |
| | |
| | 7) NOTE: PLEASE SEE NO RUN TIMES FOR ON-SITE FUEL WAS |
| | SUBMITTED. PLEASE SEE NFPA-20 9.6.2.2 |
| | |
| | 8) NOTE: PLEASE SEE NFPA-110 ALL, AS THE GENERATOR DOES |
| | FEED LIFE SAFETY AND LEGALLY REQUIRED LOADS. |
| | PLEASE SEE 7 FOR LOCATIONS, ELEVATIONS, ETC |
| | |
| | 9) NOTE: PLEASE SEE PERMIT # 08020653 AS THE GENERATOR |
| | APPLIED WAS FOR A JOHN DEERE GENERATOR AND THESE PLANS |
| | SUBMITTED UNDER 08020505 ARE FOR A CATERPILLAR. |
| | THE SIZE IS NOT THE SAME, ONE IS 150KW AND THE OTHER |
| | 160KW. |
| | |
| | 10) NOTE: PLEASE SEE MUCH OF THE SERVICE EQUIPMENT AS |
| | SHOWN DOES NOT CONTAIN ANY VOLTAGES. |
| | NEC ALL, NFPA AS NOTED. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE SEE NFPA-110 AS THE LIFE SAFETY |
| | SERVICE EQUIPMENT IS NOT PERMITTED INSIDE ELECTRICAL |
| | ROOM AS SHOWN.7.1.3, 7.2.2, 7.2.2.1 |
| | |
| | 12) NOTE: PLEASE SEE NO LOAD INFORMATION AND ACTUAL TAP |
| | LOCATIONS FOR NEW DP WAS LOCATED ON PLANS. |
| | THE LOAD SUMMARY FOR ( MAIN #1, HOUSE AMPACITY ) DOES |
| | NOT PROVIDE ENOUGH INFORMATION. |
| | NEC 220.87 ETC |
| | |
| | 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH |
| | RESPECT TO PROPOSED SHED. |
| | |
| | 14) NOTE: PLEASE INCLUDE PLANS WHICH THIS APPLICANT IS |
| | LICENSED. PLEASE BE SURE TO SEE NOTES UNDER OTHER |
| | PERMITS AS THESE PLANS ARE NOT CODE COMPLIANT. |
| | |
| | |
| | |
| | ** THERE ARE MANY ITEMS WHICH ARE NEEDED AND MAY VERY |
| | WELL BE COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| | BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |