Plan Review Notes
Plan Review Notes For Permit 08020500
Permit Number 08020500
Review Stop P
Sequence Number 1
Notes
Date Text
2008-02-28 10:18:00DENIED;
 1. BREAK SINK; IF DOORS ARE INSTALLED UNDER SINK THE
 DOORS MUST ROLE INTO CABINET SO THEY WILL NOT BE A
 TRIPPING PROBLEM OR INTERFER WITH APPROACH.
 2. PAGE P-1 WATER RISER DIAGRAM; WATER HAMMER ARRESTOR
 REQUIRED FOR ICE LINE,SPECOUT TYPE AND SIZE ON PLAN AND
 SHOW ON DIAGRAM. SEE FBCPLUMBING SECTION 604.9.