2008-02-27 14:14:45 
 BUILDING PLAN REVIEW
 PERMIT: 08020500
 ADD: 1920 WEKIVA WAY SUITE 301
 CONT: PHOENIX REALTY HOMES INC.
 TEL: (561)799-5900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-27-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)THE BUILDING CONSTRUCTION TYPE FOR THE BASE
 BUILDING IS TYPE V-B; HOWEVER, THE PLANS FOR THE
 INTERIOR BUILD-OUT INDICATE THE BUILDING AS TYPE IIB ON
 SHEET T.1. NOTE: PER FBC 602.2 ANY WOOD USED IN TYPE
 IIB BUILDINGS SHALL BE FIRE-RETARDANT-TREATED WOOD.
  
 5)SHEET A.3 DETAIL #6 THE SLAB INFILL SHALL HAVE
 STEEL REINFORCEMENT EMBEDDED INTO THE EXISTING FLOOR TO
 PREVENT THE INFILL CONCRETE FROM FALL OUT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726