Plan Review Notes
Plan Review Notes For Permit 08020473
Permit Number 08020473
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-22 21:31:57*****DENIED*****
  
 1.PLEASE INDICATE THE USE OF THE NEW GENERATOR.IS
 IT FOR STANDBY POWER, EMERGENCY POWER, OR BOTH?
  
 2.SHOW THE LOCATION OF THE GENERATOR IN REFERENCE TO
 THE REST OF THE BUILDING.
  
 3.HOW IS MANUAL SHUT DOWM OF THE SYSTEM
 ACCOMPLISHED?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW