Plan Review Notes
Plan Review Notes For Permit 08020473
Permit Number 08020473
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-06 12:06:55** DENIEDREVIEW **
  
 1) NOTE: PLANS ARE REQUIRED TO SHOW THE FOLLOWING
 MINIMUM CODES. THERE ARE REFERENCES TO NUMEROUS OTHER
 CODES WHICH DO NOT APPLY.
 FBC 2004 W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER PER
 FLORIDA STATUTES 471.023 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FS 471.003 AS AN ARCHITECT MAY NOT
 PERFORM THE ELECTRICAL FOR 277/480V SYSTEMS.
  
 4) NOTE: PLEASE KNOW THE LOCATION OF THE GENERATOR
 NEEDS TO BE REVIEW AND GONE OVER WITH THE FIRE MARSHAL.
 PLANS DO NOT SHOW ANY SHUT DOWN OF GENERATOR AS
 REQUIRED PER 230.72, 445.18.
 ** EXAMPLE, FIRE DEPARTMENT PERSONNEL NEEDS TO SHUT
 DOWN POWER IN AN EMERGENCY YET THE GENERATOR WILL START
 UP RE-FEEDING POWER INTO THE BUILDING. HOW WILL THIS
 POWER BE TURNED OFF?
 ** FYI, SHUNT TRIPS ARE NOT PERMITTED**.
 230.76, 230.79
  
 5) NOTE: PLEASE PROVIDE A LAYOUT OF THE ROOM SHOWING
 ALL DIMENSIONS FOR UNIT AND LOCATION OF NEW TRANSFER
 SWITCH. BASED ON THE LOCATIONOF THE EXISTING
 EQUIPMENT THIS DOES NOT MEET 110.26 OR REQUIRED
 CLEARANCES PER NFPA-110CHAPTER 7.
 PLEASE SEE PLANS WHICH SHOW THE GENERATOR DIRECTLY
 IN-FRONT OF EQUIPMENT WHICH IS NOT PERMITTED.
 PLEASE SEE ALL OF CHAPTER & MORE SPECIFICALLY LOCATION
 IN 7.2
 PLEASE PROVIDE LIGHTING LEVELS PER 7.3.3 FOR MINIMUM OF
 30FT CANDLES AND ALSO AN EMERGENCY BATTERY BACK UP
 FIXTURE MEETING MINIMUM LIGHTING LEVELS.
 700.12F, 700.16 ETC
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST, SET UP, CRANE SERVICE ETC.
 THE VALUE AS APPLIED AT $24K IS LOW FOR ALL WORK AS
 SHOWNAND WORK REQUIRED BUT NOT IN DESIGN.
 FBC 108.3 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE NFPA-110 7.10.3 AND PROVIDE MORE
 INFORMATION ON EXHAUST SYSTEM. BASED ON THE PIPING
 SHOWN EXISTING AND NEW THERE IS NOT ENOUGH INFORMATION
 FOR REVIEW AND THE ITEMS LISTED IN SECTION ABOVE ARE
 NTO SHOWN. EXAMPLE: FLEXIBLE CONNECTION, RAIN-CAP ETC
  
 8) NOTE: PLEASE PROVIDE WHAT ELECTRICAL SYSTEMS THIS
 GENERATOR FEEDS. PLEASE PROVIDE RUN TIMES FOR ANY LIFE
 SAFETY OR LEGALLY REQUIRED LOADS.
 700, 701, NFPA-110 CHAPTER 4 ETC
 AS NO INFORMATION WAS SUBMITTED IT IS UNCLEAR WHAT
 CODES MAY OR MAY NOT APPLY. NOT ENOUGH TO GO ON AT THIS
 TIME.
  
 9) NOTE: PLEASE PROVIDE RISER DIAGRAM AND HOW THIS UNIT
 WILL BE WIRED IN. WHAT SIZE OF UNIT? CONDUCTORS ETC?
 PLANS SHOW RANGES FOR EQUIPMENT AND DOE NOT PROVIDE ANY
 DETAILS.
 NEC 2005
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 10) NOTE: PLEASE BE AWARE THAT A GC MAY NOT PERFORM
 ELECTRICAL SCOPE OF WORK. PLEASE KNOW THAT ELECTRICAL
 CONTRACTOR MAY REFERENCE PLANS ONCE ISSUED FOR PERMIT.
  
 PLEASE SEE BUILDING REVIEW COMMENTS WITH RESPECT TO
 STRUCTURAL COMMENTS OFADDING NEW FLOOR LOADS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]