Plan Review Notes
Plan Review Notes For Permit 08020473
Permit Number 08020473
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-08 13:50:38BUILDING PLAN REVIEW
 PERMIT: 08020473
 ADD: 1801 PBL BLVD #300
 CONT: CONSTRUCTION CENTRAL CONS CORP
 TEL: (407)498-0644
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST.
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)NUDELL ARCHITECTS NEEDS TO INDICATE THE CERTIFICATE
 OF AUTHORIZATION IN THE TITLE BLOCK. 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 5)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVAL
 FOR THE NEW LOUVER WINDOW
  
 6)THE PLANS NEED TO CLEARLY SHOW THE LOCATION OF THE
 GENERATOR IN REFERENCE TO THE REQUIRED CLEARANCE FOR
 MAINTENANCE AND REPAIR WORK. INDICATE THE DISTANCE THE
 GENERATOR WILL BE PLACED FROM THE WALLS. IF THE NEW
 GENERATOR LOADS INCREASE, A STRUCTURAL ENGINEER SHALL
 PROVIDE ENGINEERED CALCULATIONS STATING THAT THE
 EXISTING FLOOR LOAD IS CAPABLE OF SUPPORTING THE WEIGHT
 OF THE GENERATOR. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND BE OF SUFFICIENT CLARITY TO INDICATE
 THE NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM THE PROVISIONS OF THE CODE
 AND RELEVANT LAWS, ORDINANCES RULES AND REGULATIONS.
 FBC 106.1.1.
  
 7)PLEASE INDICATE WHAT MATERIALS WILL BE USED TO
 ATTACH THE ACCESS LADDER TO THE EXISTING STRUCTURE.
 INDICATE THE FIRE RESISTANCE RATING OF THE ROOM WHERE
 THE GENERATOR IS INSTALLED.
  
 8)THE CLAIMED VALUE ON THE PERMIT IS LOW. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, MECHANICAL INTERIOR FINISH
 ARCHITECTURAL AND DESIGN FEES AND OVER HEAD AND PROFIT
 EXCLUDING LAND. FBC 108.3*.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  