| Plan Review Notes For Permit 08020470 |
| Permit Number |
08020470 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-26 09:16:26 | DENIED; | | | 1. DRINKING FOUNTAIN REQUIRED PER FBC PLUMBING TABLE | | | 403.1(2B). D/F MUST MEET ACCESSIBILITY CODE SECTIONS | | | 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON PLANS. | | | 2. BATHROOM WALLS WITH IN TWO FEET OF THE TOILET SHALL | | | HAVE A SMOOTH HARD SURFACE. PAINT CAN CHIP OR SCRATCH | | | SEE FBC BUILDING SECTION 1210.2. | | | 3. PAGE P- 2.01 WATER RISER, A WATER HAMMER ARRESTOR IS | | | REQUIRED ON THE COLD WATER TO ICE MACHINE SEE PLUMBING | | | SECTION 604.9. | | | 4. JOB ADDRESS REQUIRED ON EACH PAGE PER WPB AMEND. | | | SECTION 106.1.3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|