| 2008-02-26 14:04:32 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR |
| | THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE |
| | BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY |
| | DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED. |
| | SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL |
| | REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. SEE |
| | 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES, |
| | GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF |
| | INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE |
| | BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION |
| | HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR |
| | LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION |
| | 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE |
| | PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN |
| | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| | |
| | 2} 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| | A. A CONTROL DEVICE SHALL BE INSTALLED THAT |
| | AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF |
| | ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH |
| | MULTISCENE CONTROL, IN THE FOLLOWING: |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS). |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |