| 2008-02-20 08:41:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | **NOT ALL CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF |
| | PIPE ARE INDICATED. PLEASE REFERENCE THE RED CIRCLED |
| | CUT SECTIONS HIGH LIGHTED YELLOW INDICATING THIS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | **NOT ALL PIPE SIZES OR MATERIALS ARE BEING INDICATED. |
| | |
| | |
| | 3. WHITE OUT ON PLANS IS UNACCEPTABLE PER CITY OF WPB |
| | AMENDMENTS TO CHAPTER 1, SECTION 106.1.3 QUALITY OF |
| | BUILDING PLANS. |
| | |
| | 4. AT A MINIMUM TWO SETS OF PLANS ARE REQUIRED AND |
| | THEY MUST BE CORRELATED. PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER 1, SECTION *106.1 SUBMITTAL DOCUMENTS. |
| | NOTE: THE SUBMITTED PLANS ARE NOT CORRELATED, ONE |
| | DRAWING IS INDICATING A 1" GAS SUPPLY FROM THE METER |
| | AND ANOTHER DRAWING IS INDICATING A 1-1/4" GAS SUPPLY |
| | FROM THE METER. PLEASE CORRELATE PLANS AND RESUBMIT. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |