Plan Review Notes
Plan Review Notes For Permit 08020399
Permit Number 08020399
Review Stop E
Sequence Number 5
Notes
Date Text
2008-12-09 13:27:40 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE REVISE ALL CIRCUITING ON PLANS WHICH
 WILL CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. THE
 USE OF GENERAL RECEPTACLES OR GENERAL LIGHTING IS NOT
 ACCEPTABLE. PLEASE SEE 408.4 WHICH STATES ALL
 CIRCUITING SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED.
 PLEASE ALSO SEE ITEMS SUCH AS ROOF-TOP GFI FOR A/C
 EQUIPMENT.210.63 THE FOLLOWING IS BASED ON COMMENTARY
 TAKEN DIRECTLY FROM THE NEC HANDBOOK IN SECTION 408.4.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.**
  
  
 2) NOTE: PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2.
 PLEASE REVISE LIGHTING PERFORMANCE CALCULATIONS FOR
 ITEMS REVISED ON PLANS.
 PLEASE SEE AREAS SUCH AS STORAGE WHICH INDICATES AN
 ALLOWANCE GREATER THAN THE ALLOWANCES LISTED ON TABLE
 13-415.2.B.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  