| | ** DENIED REVISION ** |
| | |
| | 1) NOTE: PLEASE REVISE ALL CIRCUITING ON PLANS WHICH |
| | WILL CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. THE |
| | USE OF GENERAL RECEPTACLES OR GENERAL LIGHTING IS NOT |
| | ACCEPTABLE. PLEASE SEE 408.4 WHICH STATES ALL |
| | CIRCUITING SHALL BE SPECIFIC TO ROOMS AND AREAS IN |
| | WHICH THEY FEED. |
| | PLEASE ALSO SEE ITEMS SUCH AS ROOF-TOP GFI FOR A/C |
| | EQUIPMENT.210.63 THE FOLLOWING IS BASED ON COMMENTARY |
| | TAKEN DIRECTLY FROM THE NEC HANDBOOK IN SECTION 408.4. |
| | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.** |
| | |
| | |
| | 2) NOTE: PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2. |
| | PLEASE REVISE LIGHTING PERFORMANCE CALCULATIONS FOR |
| | ITEMS REVISED ON PLANS. |
| | PLEASE SEE AREAS SUCH AS STORAGE WHICH INDICATES AN |
| | ALLOWANCE GREATER THAN THE ALLOWANCES LISTED ON TABLE |
| | 13-415.2.B. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |