2008-06-26 08:16:47****************PROVISO****************
 A} SHEET P-2 WATER RISER DIAGRAM: A SHUT OFF VALVE IS
 REQUIRED FOR EACH SILLCOCK (HOSE BIBB). PER FBC-2004
 PLUMBING SECTION 606.2(2). (REVISION REQUIRED)
  
 B} SHEET P-2 ELECTRIC WATER HEATER DETAIL: THE RELIEF
 VALVE DISCHARGE SHALL BE PER FBC-2004 PLUMBING SECTION
 504.6.1 AND THE WATER HEATER PAN DRAIN TERMINATION
 SHALL BE PER FBC-2004 PLUMBING SECTION 504.7.2.
 (REVISION REQUIRED)
  
 C} SHEET P-2 WATER RISER DIAGRAM: AIR CHAMBERS ARE NOT
 APPROVED, WATER-HAMMER ARRESTORS AS PER FBC- PLUMBING
 SECTION 604.9 ARE APPROVED AS NOTED ON BOTTOM OF SHEET
 P-2. (REVISION REQUIRED)
  