| Notes |
| Date |
Text |
| 2008-06-26 08:16:47 | ****************PROVISO**************** | | | A} SHEET P-2 WATER RISER DIAGRAM: A SHUT OFF VALVE IS | | | REQUIRED FOR EACH SILLCOCK (HOSE BIBB). PER FBC-2004 | | | PLUMBING SECTION 606.2(2). (REVISION REQUIRED) | | | | | | B} SHEET P-2 ELECTRIC WATER HEATER DETAIL: THE RELIEF | | | VALVE DISCHARGE SHALL BE PER FBC-2004 PLUMBING SECTION | | | 504.6.1 AND THE WATER HEATER PAN DRAIN TERMINATION | | | SHALL BE PER FBC-2004 PLUMBING SECTION 504.7.2. | | | (REVISION REQUIRED) | | | | | | C} SHEET P-2 WATER RISER DIAGRAM: AIR CHAMBERS ARE NOT | | | APPROVED, WATER-HAMMER ARRESTORS AS PER FBC- PLUMBING | | | SECTION 604.9 ARE APPROVED AS NOTED ON BOTTOM OF SHEET | | | P-2. (REVISION REQUIRED) | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: MPERSON@WPB. |
|