Plan Review Notes
Plan Review Notes For Permit 08020399
Permit Number 08020399
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-29 09:15:12** DENIED 2ND REVIEW **
  
 ** SECOND REVIEW UNDER NEW PERMIT APPLICATION.
  
 ** PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING. PLEASE SEE SOME
 NEW COMMENTS BASED ON REVISED PLANS, REVISED SCOPE OF
 WORK AT LOCATION.
  
 1) NOTE: PLEASE KNOW AS STATED ON PREVIOUS ELECTRICAL
 REVIEW THE BASE BUILDING/SHELL PLANS HAVE NOT BEEN
 ISSUED FOR PERMITTING OF BASE BUILDINGS ELECTRICAL
 SYSTEMS. THIS MAY AFFECT THE BUILD OUT PLANS FOR
 ELECTRICAL DESIGNATIONS OF EQUIPMENT ETC.
 PLEASE BE SURE ALL COORDINATION IS ADDRESSED BETWEEN
 PERMITS. ANY REVISIONS MADE TO BASE BUILDING NEED TO BE
 COORDINATED WITH BUILD OUT PLANS AND VICE-VERSA.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK FOR BUILD OUT HAS STILL NOT BEEN ADJUSTED. THIS
 SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN
 COSTS ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THIS SHALL INCLUDE LIGHTING, LIGHTING
 SYSTEMS, EQUIPMENT ETC.
 FBC 108.3
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2.ABC.1.1,
 .1.2, .1.3 AND 13-415.2.
 AS STATED ON ALL PREVIOUS REVIEWS, PLEASER BE SURE
 *ALL* INFORMATION ON PLANS WITH RESPECT TO LIGHTING AND
 ALL OTHER BUILDING COMPONENTS COORDINATES WITH THE
 INPUT DATA REPORT/ SUMMARY SHEETS OF THE SUBMITTED
 ENERGY CALCULATIONS. THE INPUT DATA REPORT WILL BE
 NOTED AS IDR FOR THE REMAINDER OF THIS COMMENT.
 THE INFORMATION ON THE IDR STILL DOES CORRELATE WITH
 PLANS. THERE WILL BE SOME EXAMPLES GIVEN BELOW. HOWEVER
 THESE ARE ONLY SOME EXAMPLES. THIS IS NOT AN
 EXHAUSTIVE/EXHAUSTED LIST.
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTS FOR SPACES CALLED OUT AS
 UTILITY ROOMS. IT SEEMS ALL THREE OF THESE ROOMS ARE
 BEING LUMPED INTO ONE SPACE DESIGNATION WHICH IS OK TO
 DO. HOWEVER HOW IS THIS POSSIBLE WHEN ALL THREE
 FIXTURES ARE DIFFERENT AND CONTAIN DIFFERENT WATTAGES?
 PLEASE SEPARATE SPACES IF ALL FIXTURES ARE NOT GOING TO
 BE THE SAME.
 METHOD B, PER TABLE 13-415.2.B SPACE BY SPACE IS TO BE
 SHOWN AS SPACE BY SPACE.
 FOR EXAMPLE:
 PLEASE EXPLAIN WHERE SOME FIXTURES ON PLANS ARE LOCATED
 IN THE IDR. ONE FIXTURE IS THE DOCK LIGHT WHICH IS A
 90W FIXTURE. THERE ARE NO 90W FIXTURES SHOWN ON THE
 IDR.
 FOR EXAMPLE:
 PLEASE SEE ROOMS 105/107 WHICH ARE SEPARATE ROOMS. BOTH
 OF THESE ROOMS AND FIXTURES ARE LISTED ON THE IDR IN
 ONE SPACE.
 FOR EXAMPLE:
 PLEASE SEE THE RETAIL SALES AREA. PLEASE SEE THE COUNT
 OF THE FIXTURES LISTED AS *B* ARE LOWER ON THE IDR THAN
 THE NUMBER OF FIXTURES ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE EXTERIOR LIGHTS AS THE *J* FIXTURES AS
 LISTED ON THE FIXTURE LEGEND AND ON PLANS DOES NOT
 APPEAR IN THE IDR AT ALL. IN FACT THERE ARE NO 175W
 FIXTURES.
 FOR EXAMPLE:
 PLEASE EXPLAIN THE ELECTRICAL SYMBOL LEGEND ON SHEET
 E-8 WHICH CONTAINS DIFFERENT FIXTURES AND DESIGNATIONS
 THAN THAT OF THE FIXTURES ON THE SAME PAGE ON LIGHTING
 LEGEND.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH DOES NOT CONTAIN ANY
 ELECTRICAL WATER HEATER YET THE PLANS MOST CERTAINLY
 DOES SHOW A WATER HEATER. THE IDR IS ACTUALLY *BLANK*
 FOR THE SECTIONS FOR WATER HEATERS.
 ** IMPORTANT, PLEASE BE SURE TO SEE ALL OTHER BUILDING
 COMPONENTS. THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO
 PLEASE BE SURE TO CORRELATE ALL ITEMS ON PLANS WITH
 THAT OF THE IDR.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR
 INTERIOR AND PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR.
  
 4) NOTE: PLEASE SEE SHEET E-4 WHICH STATES THE NEW OVER
 HEAD FEEDERS WILL BE GOING TO A MAIN ELECTRICAL ROOM.
 PLEASE ADJUST AND COORDINATE PLANS AS THE MAIN
 ELECTRICAL ROOM WHICH USED TO BE ON THE BASE BUILDING
 IS NO LONGER PART OF THE BASE BUILDING DESIGN.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING
 GIVEN AT THIS TIME. THIS IS ONLY A NOTICE.
  
 6) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN
 THE LEFT HAND SIDE OF PLANS. THESE SHOULD BE PLACED IN
 BINDER(S)/ FOLDERS IN A NEAT AND ORDERLY FASHION.
 AS STATED ON PREVIOUS REVIEW: PLEASE BE SURE TO REMOVE
 ALL DOCUMENTS FROM PREVIOUS EXPIRED PERMIT APPLICATION.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  