| 2008-05-29 09:15:12 | ** DENIED 2ND REVIEW ** |
| | |
| | ** SECOND REVIEW UNDER NEW PERMIT APPLICATION. |
| | |
| | ** PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING. PLEASE SEE SOME |
| | NEW COMMENTS BASED ON REVISED PLANS, REVISED SCOPE OF |
| | WORK AT LOCATION. |
| | |
| | 1) NOTE: PLEASE KNOW AS STATED ON PREVIOUS ELECTRICAL |
| | REVIEW THE BASE BUILDING/SHELL PLANS HAVE NOT BEEN |
| | ISSUED FOR PERMITTING OF BASE BUILDINGS ELECTRICAL |
| | SYSTEMS. THIS MAY AFFECT THE BUILD OUT PLANS FOR |
| | ELECTRICAL DESIGNATIONS OF EQUIPMENT ETC. |
| | PLEASE BE SURE ALL COORDINATION IS ADDRESSED BETWEEN |
| | PERMITS. ANY REVISIONS MADE TO BASE BUILDING NEED TO BE |
| | COORDINATED WITH BUILD OUT PLANS AND VICE-VERSA. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK FOR BUILD OUT HAS STILL NOT BEEN ADJUSTED. THIS |
| | SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN |
| | COSTS ETC EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. THIS SHALL INCLUDE LIGHTING, LIGHTING |
| | SYSTEMS, EQUIPMENT ETC. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2.ABC.1.1, |
| | .1.2, .1.3 AND 13-415.2. |
| | AS STATED ON ALL PREVIOUS REVIEWS, PLEASER BE SURE |
| | *ALL* INFORMATION ON PLANS WITH RESPECT TO LIGHTING AND |
| | ALL OTHER BUILDING COMPONENTS COORDINATES WITH THE |
| | INPUT DATA REPORT/ SUMMARY SHEETS OF THE SUBMITTED |
| | ENERGY CALCULATIONS. THE INPUT DATA REPORT WILL BE |
| | NOTED AS IDR FOR THE REMAINDER OF THIS COMMENT. |
| | THE INFORMATION ON THE IDR STILL DOES CORRELATE WITH |
| | PLANS. THERE WILL BE SOME EXAMPLES GIVEN BELOW. HOWEVER |
| | THESE ARE ONLY SOME EXAMPLES. THIS IS NOT AN |
| | EXHAUSTIVE/EXHAUSTED LIST. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR LIGHTS FOR SPACES CALLED OUT AS |
| | UTILITY ROOMS. IT SEEMS ALL THREE OF THESE ROOMS ARE |
| | BEING LUMPED INTO ONE SPACE DESIGNATION WHICH IS OK TO |
| | DO. HOWEVER HOW IS THIS POSSIBLE WHEN ALL THREE |
| | FIXTURES ARE DIFFERENT AND CONTAIN DIFFERENT WATTAGES? |
| | PLEASE SEPARATE SPACES IF ALL FIXTURES ARE NOT GOING TO |
| | BE THE SAME. |
| | METHOD B, PER TABLE 13-415.2.B SPACE BY SPACE IS TO BE |
| | SHOWN AS SPACE BY SPACE. |
| | FOR EXAMPLE: |
| | PLEASE EXPLAIN WHERE SOME FIXTURES ON PLANS ARE LOCATED |
| | IN THE IDR. ONE FIXTURE IS THE DOCK LIGHT WHICH IS A |
| | 90W FIXTURE. THERE ARE NO 90W FIXTURES SHOWN ON THE |
| | IDR. |
| | FOR EXAMPLE: |
| | PLEASE SEE ROOMS 105/107 WHICH ARE SEPARATE ROOMS. BOTH |
| | OF THESE ROOMS AND FIXTURES ARE LISTED ON THE IDR IN |
| | ONE SPACE. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE RETAIL SALES AREA. PLEASE SEE THE COUNT |
| | OF THE FIXTURES LISTED AS *B* ARE LOWER ON THE IDR THAN |
| | THE NUMBER OF FIXTURES ON PLANS. |
| | FOR EXAMPLE: |
| | PLEASE SEE EXTERIOR LIGHTS AS THE *J* FIXTURES AS |
| | LISTED ON THE FIXTURE LEGEND AND ON PLANS DOES NOT |
| | APPEAR IN THE IDR AT ALL. IN FACT THERE ARE NO 175W |
| | FIXTURES. |
| | FOR EXAMPLE: |
| | PLEASE EXPLAIN THE ELECTRICAL SYMBOL LEGEND ON SHEET |
| | E-8 WHICH CONTAINS DIFFERENT FIXTURES AND DESIGNATIONS |
| | THAN THAT OF THE FIXTURES ON THE SAME PAGE ON LIGHTING |
| | LEGEND. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR WHICH DOES NOT CONTAIN ANY |
| | ELECTRICAL WATER HEATER YET THE PLANS MOST CERTAINLY |
| | DOES SHOW A WATER HEATER. THE IDR IS ACTUALLY *BLANK* |
| | FOR THE SECTIONS FOR WATER HEATERS. |
| | ** IMPORTANT, PLEASE BE SURE TO SEE ALL OTHER BUILDING |
| | COMPONENTS. THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO |
| | PLEASE BE SURE TO CORRELATE ALL ITEMS ON PLANS WITH |
| | THAT OF THE IDR. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR |
| | INTERIOR AND PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR. |
| | |
| | 4) NOTE: PLEASE SEE SHEET E-4 WHICH STATES THE NEW OVER |
| | HEAD FEEDERS WILL BE GOING TO A MAIN ELECTRICAL ROOM. |
| | PLEASE ADJUST AND COORDINATE PLANS AS THE MAIN |
| | ELECTRICAL ROOM WHICH USED TO BE ON THE BASE BUILDING |
| | IS NO LONGER PART OF THE BASE BUILDING DESIGN. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING |
| | GIVEN AT THIS TIME. THIS IS ONLY A NOTICE. |
| | |
| | 6) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN |
| | THE LEFT HAND SIDE OF PLANS. THESE SHOULD BE PLACED IN |
| | BINDER(S)/ FOLDERS IN A NEAT AND ORDERLY FASHION. |
| | AS STATED ON PREVIOUS REVIEW: PLEASE BE SURE TO REMOVE |
| | ALL DOCUMENTS FROM PREVIOUS EXPIRED PERMIT APPLICATION. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |