| Plan Review Notes For Permit 08020399 |
| Permit Number |
08020399 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-02 11:18:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SEE A1, CONDITION TYPE P8, STATES PLYWOOD TO 8' IN | | | ELECTRIC ROOM, WHICH IS IN CONFLICT WITH A9, PARTITION | | | TYPE 3A AND 3B.PLEASE CORRELATE. | | | | | | 2.THE MEP SHEETS STILL SHOW THE COMPANY NAME OF | | | STEVEN L COHEN & ASSOCIATES PA.THIS NAME IS ALSO | | | INCLUDED ON THE COVER SHEET.PLEASE INCLUDE THE | | | CERTIFICATE OF AUTHORIZATION FS481 OR REMOVE THE NAME | | | AS DISCUSSED. | | | | | | 3.SEE THE PREVIOUS LIST IN REGARDS TO ENERGY CALCS. | | | THE PREVIOUS LIST STATED THAT THE HOT WATER HEATER WAS | | | NOT INCLUDED IN THE INPUT DATA REPORT; THIS DOES NOT | | | APPEAR ON THE NEW ENERGY CALCS.PLEASE CONFIRM THAT | | | ALL BUILDING COMPONENTS ARE INCLUDED AND CORRELATE WITH | | | THE PLANS. | | | | | | 4.PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY | | | CALCS. | | | | | | | | | | | | |
|