Date Text
2008-06-02 11:18:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE A1, CONDITION TYPE P8, STATES PLYWOOD TO 8' IN
 ELECTRIC ROOM, WHICH IS IN CONFLICT WITH A9, PARTITION
 TYPE 3A AND 3B.PLEASE CORRELATE.
  
 2.THE MEP SHEETS STILL SHOW THE COMPANY NAME OF
 STEVEN L COHEN & ASSOCIATES PA.THIS NAME IS ALSO
 INCLUDED ON THE COVER SHEET.PLEASE INCLUDE THE
 CERTIFICATE OF AUTHORIZATION FS481 OR REMOVE THE NAME
 AS DISCUSSED.
  
 3.SEE THE PREVIOUS LIST IN REGARDS TO ENERGY CALCS.
 THE PREVIOUS LIST STATED THAT THE HOT WATER HEATER WAS
 NOT INCLUDED IN THE INPUT DATA REPORT; THIS DOES NOT
 APPEAR ON THE NEW ENERGY CALCS.PLEASE CONFIRM THAT
 ALL BUILDING COMPONENTS ARE INCLUDED AND CORRELATE WITH
 THE PLANS.
  
 4.PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS.
  
  
  
  