| 2008-03-20 11:07:23 | PLUMBING PLAN REVIEW: |
| | DENIED |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A0.1 CODE ANALYSIS IS INDICATING THE WRONG |
| | CODE CYCLE AS FBC-2004 W/06 REVISIONS. THE REVISIONS |
| | SHOULD BE 2007. |
| | |
| | 2. SHEET A7 DETAIL 2, CLEARLY INDICATE THE REQUIRED |
| | CLEAR FLOOR SPACE FOR THE LAVATORIES (30" X 48" AND |
| | MAXIMUM 19" UNDER LAV.) IN THE MENS AND WOMENS HANDICAP |
| | STALLS. PER FBC CHAPTER 11, SECTION 11-4.19.3. NOTE: |
| | THE DOOR SWING CAN NOT BE IN THE CLEAR FLOOR SPACE. PER |
| | FBC CHAPTER 11, SECTION 11-4.22.2. |
| | |
| | 3. SHEET A7 DETAIL 8, THE URINAL ELEVATION FOR THE |
| | MAXIMUM DISTANCE FOR THE URINAL RIM FROM FINNISH FLOOR |
| | IS BEING INDICATED WRONG AS 1'-7". THE CORRECT DISTANCE |
| | SHOULD BE 17". PER FBC CHAPTER 11, SECTION 11-4.18.2. |
| | |
| | 4. SHEET P-1, STAPLES INDICATES EXISTING 6" AND 8" RD |
| | (ROOF DRAINS), HOWEVER PREVIOUS PERMIT INFORMATION |
| | INDICATES THE EXISTING BUILDING BEING DEMOLISHED. NOTE: |
| | PERMIT #07070444 PERMIT APPLICATION WHICH IS A |
| | FOUNDATION AND SHELL PERMIT FOR THIS "STAPLES" ALSO DID |
| | NOT INDICATE THE 6" AND 8" RD (ROOF DRAINS). PLEASE |
| | CORRELATE THE RESUBMITTED PLANS TO REFLECT WHAT IS |
| | ACTUALLY BEING BUILT. PER W.P.B. SECTION 106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. SHEET P-1, STAPLES INDICATES EXISTING 4" AND 3" |
| | SANITARY LINES IN A BUILDING THAT HAS BEEN DEMOED. |
| | HOWEVER THESE SANITARY LINES WERE ADDED ON A REVISION |
| | ON PERMIT #07070444 WHICH WAS SUBMITTED 3/13/08 WHICH |
| | IS AFTER THE SUBMITTED DATE (2/19/08) OF THIS INTERIOR |
| | BUILDOUT. PLEASE CORRELATE THE RESUBMITTED PLANS TO |
| | REFLECT WHAT IS ACTUALLY BEING BUILT AND TO WHICH |
| | PERMIT NUMBER THE EXISTING WORK WAS BUILT TO AVOID TIME |
| | CONSUMING PLAN REVIEW RESEARCH. PER W.P.B., SECTION |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. SHEET P-1, RTU CONDENSATE DRAIN LINES ARE BEING |
| | INDICATED AS DRAINING INTO EXISTING ROOF DRAINS (WHICH |
| | WERE DEMOED, SEE COMMENT #4). PER FBC PLUMBING SECTION |
| | 314.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL |
| | COOLING COILS SHALL BE CONVEYED FROM THE DRAIN PAN TO |
| | AN APPROVED PLACE OF DISPOSAL. ROOF DRAINS ARE NOT AN |
| | APPROVED METHOD OF DISPOSAL. PLEASE INDICATE CONDENSATE |
| | DISPOSAL INTO A DRY WELL, CATCH BASIN, OR PLANTED AREA. |
| | |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |