Plan Review Notes
Plan Review Notes For Permit 08020399
Permit Number 08020399
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-05 14:45:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS SUBMITTED ARE THE WRONG VERSION,
 THEY NEED TO BE THE 2.5 VERSION, PER 2004 FBC
 13-400.3.A. AN ACCURATELY COMPLETED FORM 400A-04R
 (GENERATED BY THE FLA/COM-2004 COMPUTER PROGRAM,
 VERSION 2.5) DEMONSTRATING THAT CODE COMPLIANCE HAS
 BEEN ACHIEVED SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL FOR METHOD A COMPLIANCE. CALCULATIONS SHALL BE
 PERFORMED FOR THE CLIMATE ZONE IN WHICH THE BUILDING
 WILL BE LOCATED AND ACCORDING TO THE PROCEDURES
 SPECIFIED FOR METHOD A IN THIS SUB-CHAPTER
  
 2)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT THE MODEL NUMBERS OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1.
  
 3)A/C SYSTEM #5 RTU-5 LISTED ON A/C EQUIPMENT
 SCHEDULE SHOWS 10 SEER PER 2004 FBC ENERGY EFFICIENCY
 CHAPTER 13 TABLE 13-407.1.ABC.3.2A THE MINIMUM SEER FOR
 THIS SIZE SYSTEM IS 13, PLEASE CORRECT.
  
 4) UNITS RTU1 TO 4 REQUIRE SMOKE DETECTORS, PER 2004
 FBC/M 606.2.1. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]