| 2008-03-05 14:45:54 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS SUBMITTED ARE THE WRONG VERSION, |
| | THEY NEED TO BE THE 2.5 VERSION, PER 2004 FBC |
| | 13-400.3.A. AN ACCURATELY COMPLETED FORM 400A-04R |
| | (GENERATED BY THE FLA/COM-2004 COMPUTER PROGRAM, |
| | VERSION 2.5) DEMONSTRATING THAT CODE COMPLIANCE HAS |
| | BEEN ACHIEVED SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL FOR METHOD A COMPLIANCE. CALCULATIONS SHALL BE |
| | PERFORMED FOR THE CLIMATE ZONE IN WHICH THE BUILDING |
| | WILL BE LOCATED AND ACCORDING TO THE PROCEDURES |
| | SPECIFIED FOR METHOD A IN THIS SUB-CHAPTER |
| | |
| | 2)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD |
| | NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE |
| | CORRECT THE MODEL NUMBERS OR SUBMIT AN ARI CERTIFICATE, |
| | SEE 2004 FBC 13-407.1.ABC.3.1.1. |
| | |
| | 3)A/C SYSTEM #5 RTU-5 LISTED ON A/C EQUIPMENT |
| | SCHEDULE SHOWS 10 SEER PER 2004 FBC ENERGY EFFICIENCY |
| | CHAPTER 13 TABLE 13-407.1.ABC.3.2A THE MINIMUM SEER FOR |
| | THIS SIZE SYSTEM IS 13, PLEASE CORRECT. |
| | |
| | 4) UNITS RTU1 TO 4 REQUIRE SMOKE DETECTORS, PER 2004 |
| | FBC/M 606.2.1. PLEASE CORRECT. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |