Plan Review Notes
Plan Review Notes For Permit 08020399
Permit Number 08020399
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-08 11:43:28** NOTE ADDED**
  
 1) NOTE: PLEASE VERIFY ALL PANELS WHICH ARE SHWON AS
 FEED-THRU LUGS. SOME PANELS ARE SHOWN AS FEED-THRU YET
 THERE ARE OCP DEVICES IN THOSE SAME PANELS FOR SUB
 PANELS. (P4)
2008-03-07 11:35:28** DENIED REVIEW **
  
 *** FIRST REVIEW UNDER NEW APPLIED PERMIT.
  
 2029 OKEECHOBEE BLVD.
  
 ** PLEASE KNOW A FULL AND COMPLETE REVIEW FOR MINIMUM
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME AS THERE
 ARE SEVERAL ITEMS STILL NEEDED TO BE COORDINATED WITH
 THE BASE BUILDING.
  
  
  
 1) NOTE: PLEASE KNOW AT THIS TIME NO PERMIT, PLANS ETC
 HAVE BEEN APPLIED FOR ANY ELECTRICAL SYSTEMS OR OTHER
 TRADES FOR ACTUAL SHELL. THE ONLY PERMIT APPLIED FOR
 AND ISSUED IS FOR STRUCTURAL OF SHELL ONLY AND NO OTHER
 WORK. NO WALLS, NO ELECTRICAL, NO PLUMBING ETC. THE
 SHELL OWNER AND CONTRACTOR HAVE BEEN NOTIFIED TO SUBMIT
 FOR PERMIT AND COMPLETE PLANS FOR SHELL.
 AS MANY ITEMS ON THESE PLANS ARE SHOWN AS EXISTING,
 THIS IS MOST DEFINITELY NOT THE CASE.
 NO BUILD OUT PLANS WILL BE ISSUED UNTIL BASE SHELL
 BUILDING PLANS AND PERMIT APPLICATION HAVE BEEN
 COMPLETED, SUBMITTED AND ISSUED FOR PERMIT.
 ** THIS WILL AFFECT OTHER ITEMS ON REVIEWS BELOW.
  
 2) NOTE: PLEASE SEE THESE PLANS ARE NOW BEING SUBMITTED
 UNDER COMPLETELY NEW PERMIT. MANY DOCUMENTS AND SHEETS
 IN PACKAGE STILL REFLECT PREVIOUS EXPIRED PERMIT.
 PLEASE ONLY SUBMIT RELEVANT DOCUMENTS FOR NEW PERMIT
 APPLICATION BEING MADE. PLEASE KNOW THAT SOMECOMMENTS
 FROM THE THREE PREVIOUS REVIEWS UNDER EXPIRED PERMIT
 ARE STILL ALSO IN NEED OF ADDRESSING AND HAVE BEEN
 REPEATED IN THIS REVIEW. PLEASE SEE FLORIDA STATUTES
 553.80(2)(B) WAS GIVEN ON TWO PREVIOUS REVIEWS WITH
 RESPECT TO REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE.
 THE RESPONSE LETTER MENTIONS TO BE HANDLED BY THE
 OWNER/CONTRACTOR. THIS IS THE SOLE RESPONSIBILITY OF
 THE DESIGNER AND NOT AN OWNER OR CONTRACTOR. THE
 FLORIDA STATUTE AND FINE GIVEN WAS TO THE DESIGNER AS
 REQUIRED UNDER THE STATUTE GIVEN AND IS NOT THAT FOR
 ANY OTHER INDIVIDUAL.
 IT IS IMPERATIVE THAT THE MINIMUM CODE COMPLIANCE
 COMMENTS ARE ADDRESSED FOR REVIEWS.
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR SCOPE OF WORK
 IS LOW. THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST ETC. FBC 108.3
 THIS INCLUDES ALL ELECTRICAL, LIGHTING FIXTURES,
 SERVICE EQUIPMENT ETC EVEN IF ANY OF THE ABOVE ITEMS
 ARE OWNER SUPPLIED.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL SERVICE DOES NOT
 MATCH WITH ANY PLANS FOR BASE BUILDING IN PART OF THE
 FACT THAT NO PLANS HAVE BEEN SUBMITTED.
 PLEASE ALSO SEE THE SHEET E-7 SHOWS AN MSB PANEL WHICH
 SHOWS EACH TENANT BAY BEING FED FROM THIS MSB YET THE
 SAME SHEET SHOWS THIS TENANT FED FROM GUTTER AND ALSO
 FROM A SEPARATE RISER.
 PLEASE CORRELATE ALL SERVICE EQUIPMENT ONCE PLANS FOR
 BASE BUILDING ARE COMPLETED.
 230.70,230.71,230.72, 230.76, 230.79 ETC
  
 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT MEET THE MINIMUM REQUIREMENTS OF CHAPTER 13.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE METHOD *A*
 WHICH IS FOR WHOLE BUILDING. HOW IS THIS POSSIBLE WHEN
 THIS IS FOR A TENANT BUILD OUT?
 PLEASE SEE THE CALCULATIONS SUBMITTED IS NOT THE LATEST
 VERSION ADOPTED BY THE FBC 2004W /2007 SUPPLEMENTS. THE
 LATEST VERSION SHALL BE 2.5. (2.11 SUBMITTED)
 PLEASE SEE BLUE SHEETS UNDER THE ADOPTED CHANGES DATED
 DECEMBER 8TH, 2006.
 PLEASE SEE THE INPUT DATA REPORT WHICH WILL BE NOTED AS
 THE IDR ON HERE OUT DOES NOT CORRELATE WITH THE PLANS.
 FOR EXAMPLE:
 SEE ADDRESS ON CALCULATIONS SHOWS 2015 OKEECHOBEE BLVD
 WHEN APPLIED LOCATION IS 2015 OKEECHOBEE BLVD.
 THE INTERIOR LIGHTING CONTROLS FOR ALL AREAS ARE NOTED
 AS *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE
 LIGHTING IS AUTOMATICALLY CONTROLLED?
 THE EXTERIOR LIGHTING ON THE IDR SHOWS ABSOLUTELY NOT
 FIXTURES FOR EXTERIOR OF BUILDING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CLEARLY SHOW LIGHTS?
 PLEASE SEE THE INTERIOR LIGHTING FIXTURES FOR ALL
 NUMBERS OF FIXTURES, TYPE OF FIXTURES AND WATTAGES NEED
 TO CORRELATE.
 13-400.3, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3
  
 6) NOTE: PLEASE SUBMIT COMPLETED INFORMATION FOR THE
 REQUIRED AND PROPOSED LIGHTING CONTROL SYSTEM PER
 13-415.1.ABC.1.1, .1.2 ,.1.3 AND .1.4.
 RESPONSE MENTIONS THERE WILL BE A PANEL AND SOME
 DEVICES ARE SHOWN AND NOTED ON PLANS, HOWEVER NOT ALL
 INFORMATION AS REQUESTED ON THE PREVIOUS THREE REVIEWS
 UNDER EXPIRED PERMIT WAS SUBMITTED.
 SHOW COMPLETE SYSTEM
 SHOW ALL OVER RIDE LOCATIONS.
 SHOW ZONES,
 SHOW ALL LOCATIONS FOR SEPARATE CONTROLS. THERE ARE
 STILL LOCATIONS ON PLANS IN WHICH NO SEPARATE SPACE
 CONTROLS ARE PROVIDED. (WOULD GIVE ROOM OR AREA
 LOCATIONS HOWEVER E-5 DOES NOT SHOW ANY DESIGNATIONS.)
 SHOW SCHEDULING.
 ETC.
 THE RESPONSE MENTIONS THE SYSTEM WILL MEET THE FBC
 HOWEVER MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM
 DETAILS.
 WHERE ARE CONTROLS FOR OUTSIDE LIGHTING MEETING SECTION
 NOTED ABOVE? TIME CLOCK? BATTERY BACK UP FOR TIME
 CLOCK?(MIN 10HRS)OR WILL ALL BE PHOTO-SENSOR?
  
 7) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN NOTES FOR
 CONSTRUCTION DOCUMENTS AS STATED IN 13-413.1.ABC.2.1,
 .2.2.
 PLEASE PLACE REQUIRED NOTES ON PLANS.
  
 8) NOTE: PLEASE INCLUDE AND SHOW ALL ROOM AND AREA
 DESIGNATIONS ON PLANS.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE PANEL P1 IS STILL BEING SHOWN ON
 RISER WITH A 150MCB AND ON PANEL SCHEDULE AS 100 MCB.
 THIS WAS NOTED ON PREVIOUS REVIEWS
  
 10) NOTE: PLEASE BE SURE TO LIST THE FOLLOWING CODES ON
 ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA- 70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2008-03-06 17:56:482008-03-06 17:56:48
  
 IN ELEC FOR REVIEW