| 2008-03-08 11:43:28 | ** NOTE ADDED** |
| | |
| | 1) NOTE: PLEASE VERIFY ALL PANELS WHICH ARE SHWON AS |
| | FEED-THRU LUGS. SOME PANELS ARE SHOWN AS FEED-THRU YET |
| | THERE ARE OCP DEVICES IN THOSE SAME PANELS FOR SUB |
| | PANELS. (P4) |
| 2008-03-07 11:35:28 | ** DENIED REVIEW ** |
| | |
| | *** FIRST REVIEW UNDER NEW APPLIED PERMIT. |
| | |
| | 2029 OKEECHOBEE BLVD. |
| | |
| | ** PLEASE KNOW A FULL AND COMPLETE REVIEW FOR MINIMUM |
| | CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME AS THERE |
| | ARE SEVERAL ITEMS STILL NEEDED TO BE COORDINATED WITH |
| | THE BASE BUILDING. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW AT THIS TIME NO PERMIT, PLANS ETC |
| | HAVE BEEN APPLIED FOR ANY ELECTRICAL SYSTEMS OR OTHER |
| | TRADES FOR ACTUAL SHELL. THE ONLY PERMIT APPLIED FOR |
| | AND ISSUED IS FOR STRUCTURAL OF SHELL ONLY AND NO OTHER |
| | WORK. NO WALLS, NO ELECTRICAL, NO PLUMBING ETC. THE |
| | SHELL OWNER AND CONTRACTOR HAVE BEEN NOTIFIED TO SUBMIT |
| | FOR PERMIT AND COMPLETE PLANS FOR SHELL. |
| | AS MANY ITEMS ON THESE PLANS ARE SHOWN AS EXISTING, |
| | THIS IS MOST DEFINITELY NOT THE CASE. |
| | NO BUILD OUT PLANS WILL BE ISSUED UNTIL BASE SHELL |
| | BUILDING PLANS AND PERMIT APPLICATION HAVE BEEN |
| | COMPLETED, SUBMITTED AND ISSUED FOR PERMIT. |
| | ** THIS WILL AFFECT OTHER ITEMS ON REVIEWS BELOW. |
| | |
| | 2) NOTE: PLEASE SEE THESE PLANS ARE NOW BEING SUBMITTED |
| | UNDER COMPLETELY NEW PERMIT. MANY DOCUMENTS AND SHEETS |
| | IN PACKAGE STILL REFLECT PREVIOUS EXPIRED PERMIT. |
| | PLEASE ONLY SUBMIT RELEVANT DOCUMENTS FOR NEW PERMIT |
| | APPLICATION BEING MADE. PLEASE KNOW THAT SOMECOMMENTS |
| | FROM THE THREE PREVIOUS REVIEWS UNDER EXPIRED PERMIT |
| | ARE STILL ALSO IN NEED OF ADDRESSING AND HAVE BEEN |
| | REPEATED IN THIS REVIEW. PLEASE SEE FLORIDA STATUTES |
| | 553.80(2)(B) WAS GIVEN ON TWO PREVIOUS REVIEWS WITH |
| | RESPECT TO REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE. |
| | THE RESPONSE LETTER MENTIONS TO BE HANDLED BY THE |
| | OWNER/CONTRACTOR. THIS IS THE SOLE RESPONSIBILITY OF |
| | THE DESIGNER AND NOT AN OWNER OR CONTRACTOR. THE |
| | FLORIDA STATUTE AND FINE GIVEN WAS TO THE DESIGNER AS |
| | REQUIRED UNDER THE STATUTE GIVEN AND IS NOT THAT FOR |
| | ANY OTHER INDIVIDUAL. |
| | IT IS IMPERATIVE THAT THE MINIMUM CODE COMPLIANCE |
| | COMMENTS ARE ADDRESSED FOR REVIEWS. |
| | |
| | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR SCOPE OF WORK |
| | IS LOW. THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS, |
| | EQUIPMENT, DESIGN COST ETC. FBC 108.3 |
| | THIS INCLUDES ALL ELECTRICAL, LIGHTING FIXTURES, |
| | SERVICE EQUIPMENT ETC EVEN IF ANY OF THE ABOVE ITEMS |
| | ARE OWNER SUPPLIED. |
| | |
| | 4) NOTE: PLEASE SEE THE ELECTRICAL SERVICE DOES NOT |
| | MATCH WITH ANY PLANS FOR BASE BUILDING IN PART OF THE |
| | FACT THAT NO PLANS HAVE BEEN SUBMITTED. |
| | PLEASE ALSO SEE THE SHEET E-7 SHOWS AN MSB PANEL WHICH |
| | SHOWS EACH TENANT BAY BEING FED FROM THIS MSB YET THE |
| | SAME SHEET SHOWS THIS TENANT FED FROM GUTTER AND ALSO |
| | FROM A SEPARATE RISER. |
| | PLEASE CORRELATE ALL SERVICE EQUIPMENT ONCE PLANS FOR |
| | BASE BUILDING ARE COMPLETED. |
| | 230.70,230.71,230.72, 230.76, 230.79 ETC |
| | |
| | 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT MEET THE MINIMUM REQUIREMENTS OF CHAPTER 13. |
| | PLEASE SEE THE CALCULATIONS SUBMITTED ARE METHOD *A* |
| | WHICH IS FOR WHOLE BUILDING. HOW IS THIS POSSIBLE WHEN |
| | THIS IS FOR A TENANT BUILD OUT? |
| | PLEASE SEE THE CALCULATIONS SUBMITTED IS NOT THE LATEST |
| | VERSION ADOPTED BY THE FBC 2004W /2007 SUPPLEMENTS. THE |
| | LATEST VERSION SHALL BE 2.5. (2.11 SUBMITTED) |
| | PLEASE SEE BLUE SHEETS UNDER THE ADOPTED CHANGES DATED |
| | DECEMBER 8TH, 2006. |
| | PLEASE SEE THE INPUT DATA REPORT WHICH WILL BE NOTED AS |
| | THE IDR ON HERE OUT DOES NOT CORRELATE WITH THE PLANS. |
| | FOR EXAMPLE: |
| | SEE ADDRESS ON CALCULATIONS SHOWS 2015 OKEECHOBEE BLVD |
| | WHEN APPLIED LOCATION IS 2015 OKEECHOBEE BLVD. |
| | THE INTERIOR LIGHTING CONTROLS FOR ALL AREAS ARE NOTED |
| | AS *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE |
| | LIGHTING IS AUTOMATICALLY CONTROLLED? |
| | THE EXTERIOR LIGHTING ON THE IDR SHOWS ABSOLUTELY NOT |
| | FIXTURES FOR EXTERIOR OF BUILDING. HOW IS THIS POSSIBLE |
| | WHEN THE PLANS CLEARLY SHOW LIGHTS? |
| | PLEASE SEE THE INTERIOR LIGHTING FIXTURES FOR ALL |
| | NUMBERS OF FIXTURES, TYPE OF FIXTURES AND WATTAGES NEED |
| | TO CORRELATE. |
| | 13-400.3, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3 |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETED INFORMATION FOR THE |
| | REQUIRED AND PROPOSED LIGHTING CONTROL SYSTEM PER |
| | 13-415.1.ABC.1.1, .1.2 ,.1.3 AND .1.4. |
| | RESPONSE MENTIONS THERE WILL BE A PANEL AND SOME |
| | DEVICES ARE SHOWN AND NOTED ON PLANS, HOWEVER NOT ALL |
| | INFORMATION AS REQUESTED ON THE PREVIOUS THREE REVIEWS |
| | UNDER EXPIRED PERMIT WAS SUBMITTED. |
| | SHOW COMPLETE SYSTEM |
| | SHOW ALL OVER RIDE LOCATIONS. |
| | SHOW ZONES, |
| | SHOW ALL LOCATIONS FOR SEPARATE CONTROLS. THERE ARE |
| | STILL LOCATIONS ON PLANS IN WHICH NO SEPARATE SPACE |
| | CONTROLS ARE PROVIDED. (WOULD GIVE ROOM OR AREA |
| | LOCATIONS HOWEVER E-5 DOES NOT SHOW ANY DESIGNATIONS.) |
| | SHOW SCHEDULING. |
| | ETC. |
| | THE RESPONSE MENTIONS THE SYSTEM WILL MEET THE FBC |
| | HOWEVER MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM |
| | DETAILS. |
| | WHERE ARE CONTROLS FOR OUTSIDE LIGHTING MEETING SECTION |
| | NOTED ABOVE? TIME CLOCK? BATTERY BACK UP FOR TIME |
| | CLOCK?(MIN 10HRS)OR WILL ALL BE PHOTO-SENSOR? |
| | |
| | 7) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN NOTES FOR |
| | CONSTRUCTION DOCUMENTS AS STATED IN 13-413.1.ABC.2.1, |
| | .2.2. |
| | PLEASE PLACE REQUIRED NOTES ON PLANS. |
| | |
| | 8) NOTE: PLEASE INCLUDE AND SHOW ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE PANEL P1 IS STILL BEING SHOWN ON |
| | RISER WITH A 150MCB AND ON PANEL SCHEDULE AS 100 MCB. |
| | THIS WAS NOTED ON PREVIOUS REVIEWS |
| | |
| | 10) NOTE: PLEASE BE SURE TO LIST THE FOLLOWING CODES ON |
| | ELECTRICAL PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA- 70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHERE APPLICABLE) |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE |
| | MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |