| 2008-04-09 11:48:20 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE |
| | ARCHITECTURE THROUGH A COMPANY, FS481.219(2). |
| | APPLICATION IS IN PROGRESS; THIS MUST BE APPROVED AND |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER PRINTED ON EACH |
| | SHEET PRIOR TO PERMIT ISSUANCE FAC61G1-16.004. |
| | |
| | 2. THE VALUE HAS BEEN ADJUSTED.ALSO NOTE THAT THE |
| | VALUE OF THE SHELL BUILDING HAS BEEN ADJUSTED BASED ON |
| | ICC VALUATION TABLES, SEE ATTACHED.ADDITIONAL FEES |
| | ARE REQUIRED FOR BOTH THE SHELL BUILDING AND THIS |
| | PERMIT; PLEASE PAY IMMEDIATELY.NOTE THAT INSPECTIONS |
| | CANNOT BE SCHEDULED FOR THE ISSUED PERMIT UNTIL FEES |
| | ARE PAID.THE VALUATION DECLARED BY ORIGINAL |
| | CONTRACTOR WAS TOO LOW. |
| | |
| | 3. A1, NOTE N1, NOTE IS INCOMPLETE. |
| | |
| | 4. A1, CONDITION TYPES, STATES THAT PLYWOOD WILL BE |
| | INSTALLED 6IN ABOVE THE CEILING.SEE FBC603, |
| | COMBUSTIBLES NOT PERMITTED IN TYPE I AND II BUILDINGS. |
| | THIS DOES NOT APPEAR TO FALL UNDER ANY OF THE |
| | EXEMPTIONS. |
| | |
| | 5. EXISTING ENTRY RAMP, SPECIFY SLOPE, FBC11-4.3. |
| | |
| | 6. ELEVATION 5 A6 WATER FOUNTAIN CONFLICTS WITH 3A17 |
| | AND FLOOR PLAN. |
| | |
| | 7. 8 17, URINAL, SEE FBC11-4.18.2, SHOULD BE 17INCHES. |
| | SEE PLUMBING COMMENTS. |
| | |
| | 8. THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE OF |
| | COMPLETION; THE CONTRACTOR FOR THIS TENANT SPACE IS |
| | DIFFERENT FROM THE BASE BUILDING AND WILL REQUIRE A |
| | LETTER FROM THE BASE BUILDING CONTRACTOR ALLOWING THE |
| | TENANT BUILDOUT CONTRACTOR TO START WORK ON THIS TENANT |
| | SPACE BEFORE THE C OF C FOR THE BASE BUILDING HAS BEEN |
| | ISSUED.THE DEVELOPER AND BOTH CONTRACTORS WILL BE |
| | REQUIRED TO SUBMIT A LETTER STATING THAT THEY |
| | UNDERSTAND THAT ANY DISPUTE OVER RESPONSIBILITY DOES |
| | NOT RELIEVE THEM FROM THE JOINT RESPONSIBILITY TO |
| | COMPLY WITH THE BUILDING CODE. |
| | |
| | 9. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2).PLEASE ADVISE IF A FIRE SPRINKLER PERMIT |
| | HAS ALREADY BEEN ISSUED. |
| | |
| | 10. DECLARE MAXIMUM RACK HEIGHT ON THE PLAN. |
| | |
| | 11.SEE ELECTRIC COMMENTS REGARDING ENERGY CALC |
| | VERSION.PLEASE CONFIRM ALL BUILDING COMPONENTS SUCH |
| | AS WINDOWS, DOORS, HOT WATER HEATER, INSULATION, ETC. |
| | FOR INSTANCE, NO HOT WATER HEATER IS SHOWN AND GLASS |
| | STOREFRONT IS NOT REFLECTED IN THE ENERGY CALC DOOR AND |
| | WINDOW DATA.THIS IS A STATUTORY AND FLORIDA BUILDING |
| | CODE REQUIREMENT. |