| 2008-12-31 09:19:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | NOTE: PLEASE HAVE LICENSED PLUMBING CONTRACTOR APPLY |
| | FOR PERMIT. PLEASE NOTE THAT THE VALUATION OF THIS |
| | PROJECT WILL BE INCREASED DUE TO THE NEW PLUMBING. |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED TO MEET CODE |
| | COMPLIANCE. |
| | |
| | 1. SHEET P-1 SANITARY RISER DIAGRAM: THE KITCHEN SINK |
| | SHALL DRAIN DOWNSTREAM OF THE WET VENTED BATHROOMS. PER |
| | 909.1 WET VENT PERMITTED. |
| | |
| | 2. SHEET P-1 SANITARY RISER DIAGRAM. THE WASHER IS |
| | SIZED WRONG, PLEASE CORRECT THE FOLLOWING. |
| | (A) 406.3 WASTE CONNECTION. THE AUTOMATIC CLOTHES |
| | WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR |
| | DRAINAGE STACK OF 3 INCHES IN DIAMETER. |
| | |
| | (B) 708.3.4 BASE OF STACK. A CLEANOUT SHALL BE PROVIDED |
| | AT THE BASES OF EACH WASTE OR SOIL STACK. |
| | |
| | (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| | CLEANOUTS (CLEANOUT FOR WASHING MACHINE SHALL BE |
| | LOCATED AT 4' A.F.F.) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |