| 2008-06-24 16:25:30 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 3 ALTERATION AND ADDITION |
| | EXPIRED PERMIT 05070071 |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL |
| | SIGNATURE OF THE ARCHITECT. COPIED SIGNATURES ARE NOT |
| | ACCEPTABLE. THE DATE SEAL IS AFFIXED IS ALSO REQUIRED. |
| | SEE FS 481 AND FAC 61G1-16.003. REPEAT COMMENT. |
| | |
| | 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR GLAZED FRENCH DOORS AS REQUIRED BY FAC RULE |
| | 9B-72. REPEAT COMMENT. |
| | |
| | 3) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE |
| | CASEMENT WINDOWS IS EXPIRED AND DOES NOT CORRESPOND |
| | WITH THE NOA NUMBERS LISTED ON THE FLORIDA COVER SHEET. |
| | SUBMIT THE CORRECT NOA. RULE 9B-72 |
| | |
| | 4) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED |
| | IN THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOFING |
| | WILL BE USED. SPECIFY THE FASTENING OPTION AND DESIGN |
| | PRESSURE FOR THE ASSEMBLY. SUBMIT RAS 117 CALCULATIONS |
| | FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER |
| | 7 OF THE PRODUCT APPROVAL. R905.11.3 |
| | |
| | 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE |
| | STORM PANELS IS FROM EASTERN METAL SUPPLIES AND THE |
| | PRODUCT APPROVALS ARE FROM TOWN AND COUNTRY. THE |
| | SUBSTRATE IS LISTED AS CONC. BLOCK AND THE PLANS SHOW |
| | WOOD FRAME AT SOME OF THE OPENINGS. PLEASE CORRECT. FBC |
| | R 301.2.1.2 |
| | |
| | 6) ON SHEET A-2 GENERAL NOTE SPECIFIES IMPACT RATED PGT |
| | DOORS. THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE |
| | FOR IMPACT RATED WINDOWS AND PANEL DOORS. IF WINDOWS |
| | AND DOORS ARE IMPACT RATED, THEN STORM PANELS ARE NOT |
| | REQUIRED. PLEASE CLARIFY. |
| | |
| | 7)THE ENERGY CALCULATIONS THAT WERE SUBMITTED ON FORM |
| | 600A-04R ARE TAKING A CEILING FAN CREDIT. THE ELECTRIC |
| | PLANS DO NOT SPECIFY A CEILING FAN IN THE LIVING ROOM, |
| | WHICH IS REQUIRED IF TAKING THE CREDIT. ALSO, SPECIFY |
| | THE SIZE OF THE FANS ON THE PLANS.SEE FBC |
| | 13-607.1.A.1 |
| | |
| | 8) SUBMIT BUCK DETAILS FOR THE WINDOWS AND DOORS. FBC |
| | R613.6.1.1 THE DOOR JAMB DETAIL THAT WAS SUBMITTED ON |
| | THE 8.5" X 11" SHEET, IS NOT SIGNED, SEALED AND DATED |
| | BY THE DESIGNER OF RECORD, IT DOES NOT HAVE A TITLE |
| | BLOCK IDENTIFYING THE PROJECT AND IT REFERS TO DETAIL 5 |
| | ON S7 WHICH WAS NOT SUBMITTED AS PART OF THE DOCUMENTS |
| | FOR THIS PROJECT. SEE FAC 61G1-16.003. |
| | |