| Date |
Text |
| 2008-02-20 11:27:30 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. DRAWING SUBMITTED IN PENCIL ARE UNACCEPTABLE. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION *106.1.3 |
| | QUALITY OF BUILDING PLANS. |
| | |
| | 2. BUILDING FLOOR PLANS (EXISTING AND PROPOSED) SHALL |
| | BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER. PLEASE PROVIDE DEMENSIONS OF THE BATHROOM AND |
| | THE FIXTURE SPACING. PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER 1, SECTION *106.1.3 QUALITY OF BUILDING PLANS |
| | AND FBC PLUMBING SECTION *405.3.1. |
| | |
| | 3. CLEARLY IDENTIFY ALL FIXTURES ON ALL SHEETS AND |
| | CLEARLY DESIGNATE WHAT FIXTURES ARE BEING REPLACED NEW |
| | AND WHAT FIXTURES ARE EXISTING. PER CITY OF WPB |
| | AMENDMENTS TO CHAPTER 1, SECTION *106.1.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS AND SECTION *106.1.2 |
| | ADDITIONAL DATA. |
| | |
| | 4. CLEARLY LIST ON THE PERMIT APPLICATION WHAT |
| | FIXTURES ARE BEING REPLACED WITH NEW. PER THE PERMIT |
| | APPLICATION "DESCRIBE PROJECT IN DETAIL (FAILURE TO DO |
| | SO MAY RESULT IN DELAYS)" |
| | |
| | 5. THE KITCHEN SINK CAN NOT DRAIN INTO THE BATHROOM |
| | GROUP. PER FBC PLUMBING SECTION *909.1 WET VENT |
| | PERMITTED. |
| | |
| | 6. THE VALUE IS TO LOW ON THE PERMIT APPLICATION PER |
| | FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | **THE VALUE PER MARSHALL-SWIFT CALCULATIONS SHOULD BE |
| | $2620.00. PLEASE ADJUST THE VALUE ON THE PERMIT |
| | APPLICATION AND PAY THE DIFFERENCE BEFORE THE |
| | RESUBMITTAL AND PLEASE PROVIDE THE FOLLOWING PER FS |
| | 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT IS |
| | REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - 4TH |
| | FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 7. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | END OF COMMENTS: |
| | |