| Plan Review Notes For Permit 08020351 |
| Permit Number |
08020351 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-19 11:55:02 | 2004 FBC W/2007 REVISIONS | | | STRUCTURAL REPAIRS | | | | | | DENIED BY BUILDING | | | | | | 1) A NOTICE OF COMMENCEMENT WILL BE REQUIRED. | | | | | | 2) NO UPLIFT RESISTANCE VALUES ARE PROVIDED IN THE | | | CATALOG OR STATE PRODUCT APPROVALS FOR THE SIMPSON AB66 | | | POST BASE. R301.1 DESIGN. | | | BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL | | | BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING | | | DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND | | | WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION | | | OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM | | | THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF | | | TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN | | | THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION. | | | SPECIFY CONNECTORS THAT WILL PROVIDE A CONTINOUS LOAD | | | PATH FOR WIND LOADS. | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON CONNECTORS | | | AS REQUIRED BY RULE 9B-72. | | | | | | 4) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|