Plan Review Notes
Plan Review Notes For Permit 08020283
Permit Number 08020283
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-20 18:54:20PROJECT: 700 SOUTH ROSEMARY SUITE#205/ #08020283
  
 PROJECT DETAIL: INTERIOR REMODEL /WALL AND FLOOR
 FINISHES ONLY
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION
  
 STATUS: DENIED.
  
 COMMENTS:
  
 1) AS PER THE FLORIDA EXISTING BUILDING CODE PLEASE
 INDICATE THE LEVEL OF ALTERATION
 AS PER THE FOLLOWING:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2) THE PROJECT VALUATION APPEARS TO BE LOW. PLEASE
 ADJUST THE VALUATION TO REFLECT THE ACTUAL COST.
  
 3) PLEASE PROVIDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER WITHIN THE TITLE BLOCK AS PER THE FOLLOWING:
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT
  
 4) PLEASE INDICATE WHETHER THE WOOD LAMINATE FLOORING
 (F01) WILL BE ATTACHED DIRECTLY TO THEEXISTING
 PLATFORMS OR ELEVATED WITH WOOD SLEEPERS.
  
 5) PLEASE PROVIDE TEST DATA CONFIRMING THAT THE (F04)
 ZEBRA CARPET COMPLIES WITH THE ASTM E 84:
  
 803.6.2 TEXTILE CEILING FINISH.
 WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR
 TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD
 INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY
 AUTOMATIC SPRINKLERS.
  
 6) PLEASE SUBMIT ASTM TESTING DATA FORTEXTILE WALL
 COVERING W16 ( VIOLINA 76815). SUBMITTED TEST RESULTS
 ARE FOR #74847:
  
 803.6.1 TEXTILE WALL COVERINGS.
 TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE
 COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1
 OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE
 IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  
  
  