| 2008-02-20 18:54:20 | PROJECT: 700 SOUTH ROSEMARY SUITE#205/ #08020283 |
| | |
| | PROJECT DETAIL: INTERIOR REMODEL /WALL AND FLOOR |
| | FINISHES ONLY |
| | |
| | CODE REVIEW: |
| | 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS |
| | 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS |
| | CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION |
| | |
| | STATUS: DENIED. |
| | |
| | COMMENTS: |
| | |
| | 1) AS PER THE FLORIDA EXISTING BUILDING CODE PLEASE |
| | INDICATE THE LEVEL OF ALTERATION |
| | AS PER THE FOLLOWING: |
| | |
| | 301.5 . A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE. |
| | |
| | 2) THE PROJECT VALUATION APPEARS TO BE LOW. PLEASE |
| | ADJUST THE VALUATION TO REFLECT THE ACTUAL COST. |
| | |
| | 3) PLEASE PROVIDE THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER WITHIN THE TITLE BLOCK AS PER THE FOLLOWING: |
| | |
| | 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT |
| | |
| | 4) PLEASE INDICATE WHETHER THE WOOD LAMINATE FLOORING |
| | (F01) WILL BE ATTACHED DIRECTLY TO THEEXISTING |
| | PLATFORMS OR ELEVATED WITH WOOD SLEEPERS. |
| | |
| | 5) PLEASE PROVIDE TEST DATA CONFIRMING THAT THE (F04) |
| | ZEBRA CARPET COMPLIES WITH THE ASTM E 84: |
| | |
| | 803.6.2 TEXTILE CEILING FINISH. |
| | WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR |
| | TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD |
| | INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY |
| | AUTOMATIC SPRINKLERS. |
| | |
| | 6) PLEASE SUBMIT ASTM TESTING DATA FORTEXTILE WALL |
| | COVERING W16 ( VIOLINA 76815). SUBMITTED TEST RESULTS |
| | ARE FOR #74847: |
| | |
| | 803.6.1 TEXTILE WALL COVERINGS. |
| | TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME |
| | SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| | PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE |
| | COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1 |
| | OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE |
| | IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING |
| | SYSTEM, INCLUDING ADHESIVE. |
| | |