| 2008-02-15 17:42:28 | *** DENIEDREVIEW*** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES SHALL |
| | BE STATED ON PLANS RELEVANT FOR SCOPE OF WORK. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS NEED TO SHOW HOW AND |
| | WHERE INTERIOR LIGHTING IS BEING FED, CONTROLLED ETC. |
| | PLEASE SEE NOTES FROM FIRE MARSHAL ALSO AS MINIMUM |
| | LIGHTING FOR EMERGENCY ILLUMINATION OF SOME SORT WILL |
| | BE REQUIRED PER LS 7.8 AND 7.9. |
| | PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING. |
| | PLEASE VERIFY AND STATE ON PLANS IF THERE ARE ANY OTHER |
| | EXISTING LIGHTING FIXTURES WHICH MAY BE ENERGIZED OR |
| | LOCATED AT PROPERTY. |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR |
| | EXTERIOR PER 13-415.2, 13-415.2.ABC.1.3. |
| | PLEASE BE SURE TO INCLUDE FIXTURE SCHEDULE FOR NEW |
| | FIXTURES. |
| | |
| | 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF |
| | EXTERIOR LIGHTING. |
| | |
| | 5) NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) FOR NEW |
| | LIGHTING BEING SHOWN ON PLANS. PLEASE COMPLETE THE |
| | CIRCUITS ON PLANS. BRANCH CIRCUIT(S), SIZE OF OVER |
| | CURRENT PROTECTION, CONDUCTOR SIZES ETC. |
| | 240.4, 310.16, 408.4 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE LOCATION OF THE SERVICE IS IN |
| | QUESTION AS THE SERVICE DROP APPEARS TO NOT MEET 230 |
| | PART I OR PART II. THERE IS NOT ENOUGH INFORMATION. |
| | PLEASE SEE RISER WHICH ONLY SHOWS A BOX WHICH STATES |
| | 400A SINGLE PHASE. WHAT IS THIS? THIS CAN BE ASSUMED |
| | THIS IS A METER HOWEVER PLANS NEED TO BE SPECIFIC FOR |
| | ALL ELECTRICAL EQUIPMENT. |
| | |
| | 7) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND |
| | FEEDERS ARE NOT RATED FOR THE 150AMP MAINS OR PANELS |
| | PER 310.16. |
| | ** THIS IS NOT A RESIDENCE AND 310.15B6 MAY NOT BE |
| | USED. |
| | 240.4, 310.16. |
| | |
| | 8) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT |
| | GROUNDING CONDUCTORS* ARE NOT PERMITTED AHEAD OF THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 9) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY |
| | DESIGN PROFESSIONAL. PLEASE SEE FBC 105.3.1.2, FS |
| | 481.229, 471.003, 489. |
| | |
| | 10) NOTE: PLEASE SEE PANEL *A* MAY NOT BE LOCATED IN |
| | CLOSET AS SHOWN. |
| | PLEASE SEE110.26, 240.24, 408.17 |
| | |
| | 11) NOTE: PLEASE SUBMIT THE AIC RATINGS PER 110.9. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE MISSING COLD WATER PIPE REQUIRED |
| | TO BE PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | 250.50 |
| | |
| | 13) NOTE: PLEASE CLARIFY THE CONDUITS SHOWN ON RISER. |
| | WHAT IS CMT OR EMC? |
| | 110.3, NEC 300, 320-388 |
| | |
| | 14) NOTE: PLEASE PROVIDE INFORMATION ON PLANS IF THIS |
| | IS A SHELL BUILDING AT THIS TIME. |
| | FBC 106.1.2, 106.3.5.1.2, 110 |
| | |
| | 15) NOTE: PLEASE KNOW THERE IS CURRENTLY A HOLD IN |
| | SYSTEM FOR EXPIRED PERMITS AT THIS LOCATION PER THE |
| | CHIEF BUILDING INSPECTOR. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |