Plan Review Notes
Plan Review Notes For Permit 08020254
Permit Number 08020254
Review Stop E
Sequence Number 5
Notes
Date Text
2008-08-11 08:38:31 
 **DENIED REVISION**
  
 1) NOTE: PLEASE SEE SECTIONS 13-415.1.ABC.1.1, .1.2,
 .1.3. THESE SECTIONS ARE STATED AND QUOTED ON PLANS
 HOWEVER THE REVISED PLANS NOW SHOW A LIGHTING CONTROL
 PANEL WITH RELAYS HOWEVER NO OVER RIDES AT LOCATIONS
 REQUIRED BY THE CODE IS SHOWN.
 PLEASE INDICATE THE OVER RIDES.
 PLEASE INDICATE THE LOCATIONS AS THE OCCUPANT MUST BE
 ABLE TO SEE ALL LIGHTING WHICH IS BEING CONTROLLED OR
 MEET THE EXCEPTION IN THE CODE.
 PLEASE SHOW THE LOCATIONS OF THE OVER RIDE WHERE THE
 OCCUPANT ENTERS A SPACE.
 QUOTING THE SECTIONS OF THE CODE IN LIEU OF SHOWING
 MINIMUM CODE COMPLIANCE IS NOT PERMITTED.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]