Plan Review Notes
Plan Review Notes For Permit 08020254
Permit Number 08020254
Review Stop M
Sequence Number 3
Notes
Date Text
2008-05-05 08:38:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ELECTRICAL PLAN E.2 STILL SHOWS ITEM #7 OVEN-STEAMER
 TO BE INSTALLED, PLEASE CORRECT.
  
 2) MECHANICAL PLAN SHOWS ALL MECHANICAL AS EXISTING,
 ELECTRICAL PLAN E.2 NOTE 1 STATES FOUR COMPRESSORS TO
 BE INSTALLED ON ROOF. THIS ALSO NEEDS TO BE STATED ON
 MECHANICAL PLAN M.1 AS IT IS NEW MECHANICAL WORK TO BE
 DONE, SEE 2004 FBC 106.1.1 AND 106.3.5.
  
 3) MECHANICAL PLAN M.1 NOTE #2 REFERENCES A NEW
 DISHWASHER EXHAUST DUCT, PLEASE SHOW ON PLAN OR REMOVE
 NOTE, SEE 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]