| Plan Review Notes For Permit 08020254 |
| Permit Number |
08020254 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-05-05 08:38:05 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ELECTRICAL PLAN E.2 STILL SHOWS ITEM #7 OVEN-STEAMER | | | TO BE INSTALLED, PLEASE CORRECT. | | | | | | 2) MECHANICAL PLAN SHOWS ALL MECHANICAL AS EXISTING, | | | ELECTRICAL PLAN E.2 NOTE 1 STATES FOUR COMPRESSORS TO | | | BE INSTALLED ON ROOF. THIS ALSO NEEDS TO BE STATED ON | | | MECHANICAL PLAN M.1 AS IT IS NEW MECHANICAL WORK TO BE | | | DONE, SEE 2004 FBC 106.1.1 AND 106.3.5. | | | | | | 3) MECHANICAL PLAN M.1 NOTE #2 REFERENCES A NEW | | | DISHWASHER EXHAUST DUCT, PLEASE SHOW ON PLAN OR REMOVE | | | NOTE, SEE 2004 FBC 106.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|