Plan Review Notes
Plan Review Notes For Permit 08020254
Permit Number 08020254
Review Stop E
Sequence Number 3
Notes
Date Text
2008-05-04 16:52:29** DENIED 3RD AUDIT **
  
  
 1) NOTE: PLEASE SEE THE DATES ON THE PRIVATE PROVIDER
 AFFIDAVITS DO NOT COORDINATE WITH THE SIGNED DATED AND
 SEALED PLANS.
 PLEASE SEE THE SIGNED DATED PLANS IN EACH SET OF PLANS
 IS NOT TEH SAME. IN FACT THERE ARE DIFFERENT DATES IN
 EACH ONE.
 PLEASE SEE FOR EXAMPLE.
 E-1 ON AFFIDAVIT STATES PLANS DATED 3/16/08 YET THE E-1
 SUBMITTED IS CLEARLY DATED 4/18/08.
 E-2 ON AFFIDAVIT STATES PLANS DATED 3/5/08 YET THE E-2
 SUBMITTED IS CLEARLY DATED 1/28/08.
 E-3 ON AFFIDAVIT STATES PLANS DATED 3/20/08 YET THE E-3
 SUBMITTED IS CLEARLY DATED 4/18/08
 FS 553.791
  
 2) NOTE: PLEASE BE SURE ALL SEALS RAISED AND CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL. THE RAISED
 SEAL ON E-1 AND E-2 IS VERY FAINT AND NOT EASILY READ.
 FS471.025
 PLEASE KNOW THIS OFFICE HAS NOT RECEIVED THE SIGNATURE
 VERIFICATION LETTER FOR DESIGNER OF RECORD ON
 ELECTRICAL PLANS.
 PLEASE SEE THE TWO SETS SUBMIT *STILL* CONTAIN TWO
 DIFFERENT SIGNATURES. THE SEALS ARE NOT VISBLE
 *CLEARLY* IN BOTH SETS ON ALL SHEETS.
 AS PLANS SUBMITTED TO THIS OFFICE CONTAIN MULTIPLE
 SIGNATURES THIS IS REQUIRED. PLEASE BE SURE THE LETTER
 IS ORIGINAL, SIGNED, DATED, SEALED AND IS CORRECTLY
 NOTARIZED.
 PLEASE KNOW THE SIGNATURE VERIFICATION LETTER WILL NOT
 ACCEPTABLE WITH MULTIPLE SIGNATURES ON PLANS AND
 SHEETS. PLEASE BE SURE ALL COORDIANTE WITH LETTER TO BE
 SUBMITTED.
 FS 471.023, FS117.05
  
 3) NOTE: PLEASE SEE THERE ARE NOW ATTACHED LIGHTING
 SUBMITTALS WHICH APPEAR TO BE COPIES OF MANUFACTURES
 SPECS/CUT SHEETS FOR SOME OF THE FIXTURES. THIS IS OK,
 HOWEVER ONLY SOME OF THESE CONTAIN STAMPS FROM THE
 PRIVATE PROVIDER AND NONE ARE LISTED ON THE AFFIDAVITS.
 THE SHEETS WERE NOT REQUIRED BY THIS OFFICE AND WERE
 NOT REQUIRED ON PREVIOUS AUDIT. IF THE INTENT IS TO
 HAVE THESE DOCUMENTS PART OF THE RECORD SET OF PLANS
 AND DOCUMENTS PLEASE MAKE SURE STATEMENTS ADD THESE
 SHEETS AND CONTAIN THE STAMPS FROM THE PRIVATE
 PROVIDER. IF NOT PLEASE REMOVE.
 FS 553.791
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved