Plan Review Notes
Plan Review Notes For Permit 08020254
Permit Number 08020254
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-27 17:42:01** DENIED2ND AUDIT**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS FOR
 COMPLIANCE WITH FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS NOW NOTE A LIGHTING CONTROL PANEL
 HOWEVER NO DETAILS WERE PROVIDED FOR THIS PANEL.
 PLEASE SEE NO OVER RIDES AS REQUIRED WERE SHOWN.
 PLEASE SEE NO MAXIMUM TIMES WERE SHOWN ON OVER RIDES.
 PLEASE SEE LOCATIONS OF THE OVER RIDES WHICH ARE
 REQUIRED TO BE SHOWN MUST BE LOCATED SO THE OCCUPANT
 CAN SEE THE LIGHTING WHICH IS BEING CONTROLLED.
 ** THE PLANS SHOW SWITCHES HOWEVER THESE ARE ONLY SHOWN
 AS STANDARD SWITCHES PER SYMBOL LEGEND.
  
 2) NOTE: PLEASE SEE THE LIGHTING CALCULATIONS BASED ON
 THE FIXTURES SHOWN ON FIXTURE LEGEND DOES NOT MEET
 13-415.2.ABC.1.1, .1.2.
 RESPONSE LETTER IN FACT STATES THE CODE DOES NOT APPLY.
 PLEASE SEE THE CODE SECTIONS GIVEN AS THE CODE IS FOR
 ALL LIGHTING WITH IN A *BUILDING* GREATER THAN 5K SQ
 FT. THIS *BUILDING* IS GREATER THAN 5K SQ FT AND
 AUTOMATEDLIGHTING CONTROL REQUIREMENTS AS SET FORTH
 IN THE FLORIDA BUILDING CODE DOES APPLY. THIS CAN BE
 CONFIRMED BY THE DEFINITIONS IN CHAPTER 2 OF THE FBC
 AND DEFINITIONS IN CHAPTER 13 SECTION 202.
 ANY FURTHER CONFIRMATION CAN BE GIVEN BY THE FLORIDA
 BUILDING COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS.
 DEC STATEMENTS HAVE BEEN ISSUED BY THE ABOVE ON
 PREVIOUS OCCASIONS.
 PLEASE SEE THE CODE SECTIONS REFERENCED ABOVE WHICH
 REQUIRES THE MINIMUM LEVELS TO BE FIGURED FOR EACH
 FIXTURE SHALL BE BASED ON THE FIXTURE VA RATING, NOT
 THE SIZE OF THE LIGHT BULB BEING INSTALLED.
 FOR EXAMPLE:
 THE FIXTURES AS SPECIFIED ON LEGEND FOR FIXTURE *B* IS
 SHOWN AS 100 WATTS ON PLANS, YET THIS FIXTURE IS A
 300WATT FIXTURE BASED ON THE CATALOG NUMBER AND FIXTURE
 INFORMATION GIVEN PER MANUFACTURE.
 PLEASE SEE THE FIXTURE *C* IS ACTUALLY A 150W FIXTURE
 PER MANUFACTURE BASED ON PLANS AND YET THE WATTAGE
 FIGURED IS 100 WATTS ONCE AGAIN.
 THIS WAS GONE OVER IN MEETING HELD BEFORE PLANS WERE
 RE-SUBMITTED AS THE CODE REQUIRES THE WATTAGE OF
 FIXTURE.
 PLEASE VERIFY FIXTURE *A*, AS THIS DOES NOT COORDINATE
 WITH THE MANUFACTURE'S LISTED PRODUCTS. PLEASE OBTAIN
 INFORMATION ON THESE UNITS.
 PLEASE SEE THE LIGHTING CALCULATIONS STATE J-BOX FOR
 LED LIGHTS, YET NO INFORMATION WAS PLACED ON FIXTURE
 LEGEND. HOW ARE THESE FED? LOW VOLTAGE?LINE VOLTAGE?
 LISTED, FIXTURE TYPE ON LEGEND? ETC.
 AS NO INFORMATION WAS SHOWN FOR THESE FIXTURES NO
 REVIEW OF THESE CAN BE DONE.
 FBC 106.1.2, 106.3.5.1.2
 ** IMPORTANT** PLEASE BE SURE ALL OF THESE FIXTURES AS
 NOTED ABOVE CONTAIN A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL) AS ADOPTED BY OSHA
 IN THE UNITED STATES. ONLY ONE FIXTURE AS NOTED ABOVE
 WAS FOUND TO SHOW INFORMATION AS BEING LISTED BY
 UNDERWRITERS LABORATORIES. (UL). (NEC 110.3)
 PLEASE SEE 13-415.2 AND SECTION ABOVE AND SUBMIT
 MINIMUM LIGHTING PERFORMANCE CALCULATIONS.
 I HAVE ATTACHED SOME PRINT OUTS OF THE FIXTURES FROM
 THE MANUFACTURE'S ON-LINE SPECS.
  
 3) NOTE: PLEASE KNOW OF THE ELECTRICAL PLANS NOW
 SUBMITTED SHEET E-1 NOW CONTAINS A COMPLETELY DIFFERENT
 SIGNATURE FOR THE ENGINEER OF RECORD THAN THAT OF SHOWN
 ON E-2 AND E-3.
 THESE ARE ALSO DIFFERENT FROM THE FIRST SET OF
 ELECTRICAL PLANS SUBMITTED.
 PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002. PLANS MAY ONLY BE
 SIGNED BY THE ENGINEER.
 AS SIGNATURES NOW DIFFER FROM MULTIPLE SHEETS PLEASE
 SUBMIT A SIGNATURE VERIFICATION LETTER WITH LEGAL AND
 ORIGINAL SIGNATURE ALONG WITH RAISED SEAL AND DATE.
 PLEASE BE SURE LETTER IS CORRECTLY NOTARIZED PER FS
 117.05.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 ** PLEASE BE SURE RAISED SEAL ON ALL PLANS AND
 DOCUMENTS IS CLEAR AND VISIBLE WITH ALL INFORMATION ON
 RAISED SEAL. SOME OF THESE ARE VERY FAINT AND NOT
 EASILY READ.
  
 ** ONE SET OF ELECTRICAL PLANS FOR BOTH THE ORIGINAL
 AND NEW SUBMITTED SHEETS ARE BEING RETAINED BY THIS
 OFFICE FOR FURTHER POSSIBLE ACTION.
  
 4) NOTE: PLEASE PLACE MECHANICAL DETAIL AND INFORMATION
 ON THE M SHEETS. PLEASE SEE THE SWORN AFFIDAVIT FROM
 PRIVATE PROVIDER STATES CODE COMPLIANCE FOR SHEET M-1
 HAS BEEN MET, YET SOME OFTHE MECHANICAL INFORMATION
 IS ACTUALLY ON THE ELECTRICAL SHEETS. HOW IS THIS
 POSSIBLE?
 PLEASE ADJUST PLANS FOR NEW SHEETS. THEMECHANICAL
 REVIEWER HAS MADE NOTE TO THIS AND IS AWARE OF THE NEED
 FOR CHANGE.
  
 5) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME. PLEASE BE SURE TO
 ADDRESS ALL COMMENTS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  