| Plan Review Notes For Permit 08020254 |
| Permit Number |
08020254 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-19 16:23:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN PAGE M-1 STATES 'NEW DISHWASHER | | | EXHAUST HOOD ON TOP OF DISHWASHER'. PAGES P.201, E.2, | | | FS1, FS2, AND FS3 STATE THIS APPLIANCE IS TO BE A | | | OVEN-STEAMER. PLEASE CORRECT PLANS TO COINCIDE AS A | | | PROPER REVIEW MAY NOT BE ACCURATE AT THIS TIME. | | | | | | 2) PLEASE SEE 2004 FBC/M 508.1 REGARDING MAKEUP AIR, | | | PLEASE ADDRESS. | | | | | | 3) PLEASE STATE ON MECHANICAL PLAN IF THE EXISTING | | | 12X10 EXHAUST DUCT IS SERVING ANYTHING ELSE, SEE 2004 | | | FBC/M 506.4. | | | | | | 4) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE | | | NEW IN-LINE EXHAUST FAN, SEE 2004 W.P.B. AMEND. | | | 106.1.2.. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|