| Date |
Text |
| 2008-02-12 10:11:54 | *** DENIED*** |
| | |
| | 1) NOTE: PLEASE KNOW AS PACKAGE WAS SUBMITTED FOR |
| | PRIVATE PROVIDER WHICH ALSO INCLUDED A NOTICE TO |
| | BUILDING OFFICIAL FOR INSPECTIONS AS WELL AS PLANS |
| | REVIEW NO INSPECTION QUALIFICATIONS/CERTIFICATION |
| | DOCUMENTS WERE LOCATED IN PACKAGE. |
| | PLEASE BE SURE TO SUBMIT THESE IN COMPLETE PACKAGE WHEN |
| | RESUBMITTING PLANS. |
| | FS 553.791 |
| | |
| | 2) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING |
| | LATEST ADOPTED CODES RELEVANT TO PROJECT AND DESIGN. |
| | SOME ARE ALREADY SHOWN HOWEVER PLEASE LIST THE |
| | FOLLOWING. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2002 NFPA-72 |
| | FBC 106.1.2, 106.5, FS 553.73 |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW AND EXISTING TO DETERMINE NEW |
| | LIGHTING LEVELS BEING ADDED TO EXISTING AREAS. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1..1, .1.2. |
| | |
| | 4) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS FOR NEW |
| | BEING INSTALLED PER FBC 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE KNOW THIS IS ONLY REQUIRED FOR NEW BEING |
| | INSTALLED MEETING THE PRESCRIPTIVE REQUIREMENTS OF THE |
| | CODES GIVEN. |
| | THIS DOES NOT REQUIRE EXISTING TO REMAIN TO BE MODIFIED |
| | ONLY NEW BEING INSTALLED. 13-101, 13-400.2 |
| | PLEASE INCLUDE NOTES FOR 13-413.1.ABC.2 |
| | |
| | 5) NOTE: PLEASE SEE THE 75KVA TRANSFORMER SHALL NOT BE |
| | PERMITTED ABOVE CEILING PER 450.13B. RISER STATES TO |
| | REMOVE CEILING TILES WHICH IS NOT ACCEPTABLE. |
| | THIS CONTRADICTS SHEET E-1 WHICH STATES THERE ARE NO |
| | TILES OR CEILING GRID. WHICH ONE IS IT? |
| | |
| | 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS ON EXISTING |
| | TENANT GUTTER AND MAIN SERVING GUTTER WITH EXISTING |
| | LOADS ALONG WITH NEW LOADS BEING ADDED. |
| | NEC 220.87. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 210.8B2 WHICH REQUIRES ALL 15/20AMP |
| | 120V RECEPTACLES IN KITCHEN/SERVING AREAS TO BE GFI/ |
| | GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT THESE |
| | RECEPTACLES ARE SERVING KITCHEN/SERVING COUNTER |
| | SPACES. |
| | THE PLANS ON E-1 DO CONTAIN A NOTE WHICH STATES THEY |
| | ARE TO BE GFCI, HOWEVER THE NEITHER THE DEVICES OR THE |
| | BREAKERS INDICATE THIS REQUIRED PROTECTION. |
| | THE PANEL SCHEDULES DO CONTAIN AN * ASTERISK NEXT TO |
| | MANY OF THESE HOWEVER THE PANEL SCHEDULE DOES NOT |
| | PROVIDE ANY DETAIL OR SYMBOL LEGEND FOR THE SINGLE |
| | ASTERISK WHICH STATES THIS IS FOR GFCI TYPE BREAKER. |
| | THIS SAME SINGLE ASTERISK IS NOTED ON 2-POLE CIRCUITS |
| | ALSO? |
| | |
| | 8) NOTE: PLEASE COORDINATE THE FEEDERS TO PANEL *C* |
| | WHETHER THEY ARE NEW OR ARE ALREADY EXISTING. PLEASE |
| | SEE PANEL *C* WHICH STATES ON THE BOTTOM OF PANEL THE |
| | FEEDERS ALREADY EXIST, HOWEVER AS PANEL *C* IS NEW, |
| | TRANSFORMER IS NEW AND FEEDERS ON RISER ARE NEW, HOW |
| | CAN THESE BE EXISTING? |
| | PLEASE COORDINATE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE |
| | ANY QUESTIONS, PLEASE CALL. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |