Plan Review Notes
Plan Review Notes For Permit 08020254
Permit Number 08020254
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-12 10:11:54*** DENIED***
  
 1) NOTE: PLEASE KNOW AS PACKAGE WAS SUBMITTED FOR
 PRIVATE PROVIDER WHICH ALSO INCLUDED A NOTICE TO
 BUILDING OFFICIAL FOR INSPECTIONS AS WELL AS PLANS
 REVIEW NO INSPECTION QUALIFICATIONS/CERTIFICATION
 DOCUMENTS WERE LOCATED IN PACKAGE.
 PLEASE BE SURE TO SUBMIT THESE IN COMPLETE PACKAGE WHEN
 RESUBMITTING PLANS.
 FS 553.791
  
 2) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 LATEST ADOPTED CODES RELEVANT TO PROJECT AND DESIGN.
 SOME ARE ALREADY SHOWN HOWEVER PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-72
 FBC 106.1.2, 106.5, FS 553.73
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AND EXISTING TO DETERMINE NEW
 LIGHTING LEVELS BEING ADDED TO EXISTING AREAS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1..1, .1.2.
  
 4) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS FOR NEW
 BEING INSTALLED PER FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THIS IS ONLY REQUIRED FOR NEW BEING
 INSTALLED MEETING THE PRESCRIPTIVE REQUIREMENTS OF THE
 CODES GIVEN.
 THIS DOES NOT REQUIRE EXISTING TO REMAIN TO BE MODIFIED
 ONLY NEW BEING INSTALLED. 13-101, 13-400.2
 PLEASE INCLUDE NOTES FOR 13-413.1.ABC.2
  
 5) NOTE: PLEASE SEE THE 75KVA TRANSFORMER SHALL NOT BE
 PERMITTED ABOVE CEILING PER 450.13B. RISER STATES TO
 REMOVE CEILING TILES WHICH IS NOT ACCEPTABLE.
 THIS CONTRADICTS SHEET E-1 WHICH STATES THERE ARE NO
 TILES OR CEILING GRID. WHICH ONE IS IT?
  
 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS ON EXISTING
 TENANT GUTTER AND MAIN SERVING GUTTER WITH EXISTING
 LOADS ALONG WITH NEW LOADS BEING ADDED.
 NEC 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE 210.8B2 WHICH REQUIRES ALL 15/20AMP
 120V RECEPTACLES IN KITCHEN/SERVING AREAS TO BE GFI/
 GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT THESE
 RECEPTACLES ARE SERVING KITCHEN/SERVING COUNTER
 SPACES.
 THE PLANS ON E-1 DO CONTAIN A NOTE WHICH STATES THEY
 ARE TO BE GFCI, HOWEVER THE NEITHER THE DEVICES OR THE
 BREAKERS INDICATE THIS REQUIRED PROTECTION.
 THE PANEL SCHEDULES DO CONTAIN AN * ASTERISK NEXT TO
 MANY OF THESE HOWEVER THE PANEL SCHEDULE DOES NOT
 PROVIDE ANY DETAIL OR SYMBOL LEGEND FOR THE SINGLE
 ASTERISK WHICH STATES THIS IS FOR GFCI TYPE BREAKER.
 THIS SAME SINGLE ASTERISK IS NOTED ON 2-POLE CIRCUITS
 ALSO?
  
 8) NOTE: PLEASE COORDINATE THE FEEDERS TO PANEL *C*
 WHETHER THEY ARE NEW OR ARE ALREADY EXISTING. PLEASE
 SEE PANEL *C* WHICH STATES ON THE BOTTOM OF PANEL THE
 FEEDERS ALREADY EXIST, HOWEVER AS PANEL *C* IS NEW,
 TRANSFORMER IS NEW AND FEEDERS ON RISER ARE NEW, HOW
 CAN THESE BE EXISTING?
 PLEASE COORDINATE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]