2008-02-12 22:35:56BUILDING PLAN REVIEW
 PERMIT: 08020254
 ADD: 700 S ROSEMARY # 118
 CONT: SOUTHEAST CONTRACTING
 TEL: (561)640-7422
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE THE
 CODE ANALYSIS.
  
 2) NOTE THIS PACKAGE WAS SUBMITTED UNDER PRIVATE
 PROVIDER WHICH ALSO INCLUDES NOTICE TO THE BUILDING
 OFFICIAL FOR PRIVATE PROVIDER INSPECTIONS AS WELL AS
 PLAN REVIEW. NOTE THERE HAS BEEN DOCUMENTATION AS TO
 THE QUALIFICATIONS AND LICENSURE OF THE INSPECTOR.
 PLEASE PROVIDE WHEN THE PACKAGE IS RESUBMITTED. FL S S
 553.791.
  
 3) THE COVER SHEET INDICATES THIS TO BE A TWO STORY
 BUILDING. SHEETA.201 INDICATES THIS IS A TYPE II NOT
 LISTING A OR B TYPE, PLEASE TAKE NOTE THAT THE (5)
 STORY PARKINGGARAGE AND ?B? BLOCK RETAIL ARE
 CONSIDERED ?ONE? BUILDING, MAKING THISA 5 STORY
 BUILDING. IN CONSIDERING THE MOST RESTRICTIVE OCCUPANCY
 IN THIS BUILDING, ?A3?THE MINIMUM BUILDING TYPE WOULD
 BE A TYPE I-B, PLEASE CORRECT ANALYSIS.
  
 4) THE PERMIT APPLICATION INDICATES THE GROSS SQUARE FT
 AREA TO BE 1635 SQ FT, THE PLANS INDICATE THE NET AS
 1513 SQ FT. TABLE 1004.1.2 FOR MERCANTILE TAKES THE
 GROSS SQ FOOTAGE WHICH WOULD BE AN OCCUPANT LOAD OF 55
 CREATING AN?A-2? ASSEMBLY. PLEASE CORRECT THE CODE
 ANALYSIS AS WELL AS OCCUPANCY DATA..
  
 5) WITH THE ABOVE A-2 ASSEMBLY OCCUPANCYPLEASE SEE
 TABLE 302.3.2FOR THE REQUIRED SEPARATION BETWEEN
 OCCUPANCY GROUPS, PLEASE PROVIDE WHAT TYPE OF OCCUPANCY
 IS LOCATED ON EACH SIDE OF THIS TENANT. IF OTHER THAN
 ANOTHER A-2 OCCUPANCY PLEASE PROVIDE THE OCCUPANCIES
 AND REQUIRED HR RATING OF THE OCCUPANCY SEPARATION
 WALL.
  
 6)SHEET A.201 INDICATES A RAISED PLATFORM BUT THERE
 IS NO MENTION AS WHAT TYPE OF MATERIAL THE PLATFORM
 SHALL BE CONSTRUCTED FROM?PLEASE SEE 410.4. PLATFORM
 CONSTRUCTION.
 NOR THE FLOOR LOADING?
  
 7) THE PLANS ALSO DO NOT PROVIDE A NUMBERING SCHEDULE
 FOR THE DOORS NOR IS THERE ANY SIZE PROVIDED TO SEE IF
 THE DOORS COMPLY WITH 1008.1.1 AND11-4.13.5. PLEASE
 PROVIDE SO CODE COMPLIANCE CAN BE DETERMINED .
  
 8) PLANS DO NOT INDICATE IF THIS IS A CHANGE OF
 OCCUPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION.
 106.1.2. IF THIS IS A CHANGE OF OCCUPANCY CHAPTER 8 OF
 THE FLORIDA EXISTING BUILDING CODEWOULD NEED TO BE
 REVIEWED FOR ADDITIONAL REQUIREMENTS AND IF GOING INTO
 A MORE STRINGENT OCCUPANCY CLASSIFICATION.
  
 9) POSSIBLY IF A CHANGE OF OCCUPANCY PLANS WILL NEED TO
 GO TO PALM BEACH COUNTY FOR
 REVIEW FOR IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.