| 2008-02-15 15:41:24 | *** DENIEDREVIEW*** |
| | |
| | |
| | 1) NOTE: PLEASE CLARIFY THE METHOD *B* CALCULATIONS |
| | BEING SUBMITTED FOR SPACE WHICH ALREADY HAS ASSUMPTIONS |
| | ON THE ORIGINAL PHASE PERMIT. |
| | PLEASE SEE 13-400.3.B, 13-400.2.A. WHICH INDICATES |
| | SHELL BUILDINGS. PLEASE SEE THIS SPACE DOES NOT MEET |
| | RENOVATED BUILDING SO PLEASE VERIFY METHOD SUBMITTED. |
| | THESE WERE SUBMITTED ALONG WITH SPACE BY SPACE |
| | CALCULATIONS PER 13-415.2 |
| | ** PLEASE SEE THAT IN ANY CASE THERE ARE SPACES NOTED |
| | ON THE IDR WHICH INDICATES MANUAL ON/OFF CONTROLS WHEN |
| | THESE ARE ACTUALLY AUTOMATED ON PLANS. |
| | |
| | 2) NOTE: PLEASE INCLUDE NOTES AND DESIGNS ON PLANS FOR |
| | 517.1, AND 517 PART II. |
| | |
| | 3) NOTE: PLANS SHOW NEW IT ROOM HOWEVER AT THIS TIME NO |
| | REVIEW OF ITEMS FOR THIS ROOM FALLING UNDER THE |
| | DEFINITIONS OF 645.4 CAN BE FOUND. IF THIS IS A TRUE IT |
| | ROOM PLEASE ADJUST ELECTRICAL, MECHANICAL AND BUILDING |
| | PLANS ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE SEE ANY COMMENTS UNDER OTHER SUBMITTED |
| | REVISION WHICH MAY AFFECT SPACE. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |