| 2008-02-21 15:04:39 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.PLEASE CLARIFY SCOPE OF WORK.BASED ON THE PLANS, |
| | IT APPEARS THAT THIS IS A SECOND FLOOR BUILDOUT. |
| | HOWEVER, GV102, SE CORNER, STATES "BUILDING OUTSIDE |
| | SCOPE OF WORK PERMITTED UNDER PHASE II AND PHASE III". |
| | FROM THE LANGUAGE IT APPEARS THAT THIS AREA HIGHLIGHTED |
| | IS NOT WITHIN THE SCOPE OF THIS WORK, "OUTSIDE SCOPE OF |
| | WORK", BUT I THINK THAT THE LANGUAGE MEANS EXTERIOR. IS |
| | THIS CORRECT?THE LABEL "SCOPE OF WORK" APPEARS IN |
| | TWO PLACES BUT DOESN'T POINT TO ANYTHING.SCOPE OF |
| | WORK IS CLARIFIED ON OTHER SHEETS BUT PLEASE REVISE |
| | THIS SHEET FOR CONSISTENCY. |
| | |
| | 2.ROOM 272 IS REQUIRED TO BE ADAPTABLE |
| | FBC11-4.1.3(11).PLEASE SHOW THE TURNING RADIUS, |
| | FBC11-4.22.3, CLEAR FLOOR SPACE REQUIRED FOR FIXTURES, |
| | FBC11-4.22.3.DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE FOR ANY FIXTURE FBC1104.22.2(1). LAVATORIES |
| | AND MIRRORS TO COMPLY WITH FBC11-4.19. |
| | |
| | 3.ROOM 272, PROVIDE A BACKING DETAIL FOR GRAB BARS. |
| | |
| | 4.THE STAFF TOILET ROOM, ROOM 275, IS TO BE |
| | ACCESSIBLE FBC11-4.1.3(11).THE LAVATORY AND MIRRORS |
| | TO COMPLY WITH FBC11-4.19, CLEAR FLOOR SPACE TO BE |
| | SHOWN ON THE PLAN, TURNING RADIUS FBC11-4.22.3, GRAB |
| | BARS FBC11-4.26.2. |