 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF ANY OF THE LIGHT POLES SHOWN ARE NEW,
 AND IF SO SUBMIT MANUFACTURERS SPECIFICATIONS AND WIND
 LOAD CALCULATIONS FOR REVIEW. IF ALL ARE EXISTING,
 PLEASE NOTE SAME ON THE PLAN.
  
 2} LOCATE THE "EXISTING SERVICE POINT"ON THE PLAN.
  
 3} CIRCUITS LE-6, 10,14, AND 16 ARE MISCALCULATED IN
 THE PANEL SCHEDULE PER 22014(I) SHOULD BE 3 AMPS.SEE
 CIRCUITING SHEET E-1.
  
 4} CIRCUITS LW-2, 6,8 AND 12 ARE MISCALCULATED IN THE
 PANEL SCHEDULE, SHOULD BE 6,6,3 AND 6 AMPS
 RESPECTIVELY,SEE SHEET E-2 AND PANEL SCHEDULE, SHEET
 E-4. 220.14(I).
  
 5} CIRCUITS L-2 SHOULD BE CALCULATED AT 1.5 AMPS IN THE
 SCHEDULE, SEE SHEET E-2.220.14(I).
  
 6} CIRCUIT LW-4 IS CALCULATED CORRECTLY ASSUMING THOSE
 CIRCUITS ON SHEET E-2, NORTH WEST CORNER, LABELED
 "L-4", ARE IN FACT "LW-4. PLEASE CORRECT.
  
 7} THERE ARE 2 CIRCUIT HOME RUNS LABELEDL-8 ON SHEET
 E-2, ONE AT 3 AMPS AND ONE AT 1.5 AMPS. THE PANEL
 SCHEDULE, SHEET E-5, LISTS THAT CIRCUIT AS 3AMPS.,
 CORRELATE SAME.
  
 8} IN THE "SERVICE POINT DATA" CALCULATIONS, SHEETS
 E-3,4 AND 5, THERE IS NO RECEPTACLE LOAD INCLUDED
 .220.14(I).
  
 9) COULD NOT FIND BRANCH CIRCUIT L-14 ON THE PLANS.
  
 10} CIRCUIT L-19 IS LISTED AS A SPARE IN THE PANEL
 SCHEDULE, BUT SHOWN FEEDING THREE RECEPTACLES ON SHEET
 E-2.
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  