| Plan Review Notes For Permit 08020218 |
| Permit Number |
08020218 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-11 13:08:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.THE PRODUCT APPROVALS SUBMITTED WITH THE MASTER | | | PERMIT WERE FOR JOHNS MANVILLE.FIRESTONE WAS | | | SUBMITTED WITH THIS PERMIT.PLEASE SUBMIT AS A | | | REVISION TO 05120429. | | | | | | 2.PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD, FBC*106.3.3. | | | | | | 3.SHEET S1 (MASTER PERMIT 05120429) SPECIFIES DESIGN | | | PRESSURES OF -53.33, -89.48, -134.67 FOR ZONES 1, 2, | | | AND 3.THE ASSEMBLY YOU HAVE SELECTED HAS A DESIGN | | | PRESSURE LIMITATION OF -120, NO ENHANCED FASTENING | | | ALLOWED (LIMITATION #9).PLEASE ADDRESS. | | | | | | 4.SEE BUILDING REVIEW #12 (AND CORRESPONDING FIRE | | | REVIEW), MASTER PERMIT.PLEASE ADDRESS THE COMMENT | | | REGARDING EXITING FOR THE SECOND FLOOR. | | | | | | |
|