Plan Review Notes
Plan Review Notes For Permit 08020218
Permit Number 08020218
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-11 13:08:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE PRODUCT APPROVALS SUBMITTED WITH THE MASTER
 PERMIT WERE FOR JOHNS MANVILLE.FIRESTONE WAS
 SUBMITTED WITH THIS PERMIT.PLEASE SUBMIT AS A
 REVISION TO 05120429.
  
 2.PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.
  
 3.SHEET S1 (MASTER PERMIT 05120429) SPECIFIES DESIGN
 PRESSURES OF -53.33, -89.48, -134.67 FOR ZONES 1, 2,
 AND 3.THE ASSEMBLY YOU HAVE SELECTED HAS A DESIGN
 PRESSURE LIMITATION OF -120, NO ENHANCED FASTENING
 ALLOWED (LIMITATION #9).PLEASE ADDRESS.
  
 4.SEE BUILDING REVIEW #12 (AND CORRESPONDING FIRE
 REVIEW), MASTER PERMIT.PLEASE ADDRESS THE COMMENT
 REGARDING EXITING FOR THE SECOND FLOOR.
  
  