| Plan Review Notes For Permit 08020205 |
| Permit Number |
08020205 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-11 12:53:58 | *** DENIED REVIEW *** | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED | | | ON PLANS. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | FBC ADMIN SECTION 106.1.2, 106.5, FS 553.73 | | | | | | 2) NOTE: PLEASE SEE THE TABLE *C* LIGHTING PERFORMANCE | | | CALCULATIONS SHOWN ARE OVER THE MAXIMUM ALLOWANCES PER | | | 13-415.2.C.1. | | | PLEASE ALSO SEE THE TOTAL ALLOWANCE PER TABLE *C* IS | | | 1.0 AND THE CALCULATIONS SHOW AN ALLOWANCE OF 1.1 WHICH | | | IS OVER. | | | | | | 3) NOTE: PLEASE STATE MAXIMUM TIMES ON OS DEVICES. | | | 13-415.1.ABC.1.1, .1.2. | | | | | | 4) NOTE: PLEASE VERIFY IF THERE ARE ANY SUITE/UNIT | | | NUMBER(S) OR OF THIS TENANT IS THE ENTIRE FLOOR. THIS | | | WAS APPLIED AS THE ENTIRE FLOOR. | | | THIS IS TO BE CONFIRMED AND SUITE/UNIT NEEDS TO BE | | | ADDED TO TITLEBLOCKS ONCE CONFIRMED. | | | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS, | | | PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION | | | BELOW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|