Plan Review Notes
Plan Review Notes For Permit 08020205
Permit Number 08020205
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-11 12:53:58*** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 FBC ADMIN SECTION 106.1.2, 106.5, FS 553.73
  
 2) NOTE: PLEASE SEE THE TABLE *C* LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ARE OVER THE MAXIMUM ALLOWANCES PER
 13-415.2.C.1.
 PLEASE ALSO SEE THE TOTAL ALLOWANCE PER TABLE *C* IS
 1.0 AND THE CALCULATIONS SHOW AN ALLOWANCE OF 1.1 WHICH
 IS OVER.
  
 3) NOTE: PLEASE STATE MAXIMUM TIMES ON OS DEVICES.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE VERIFY IF THERE ARE ANY SUITE/UNIT
 NUMBER(S) OR OF THIS TENANT IS THE ENTIRE FLOOR. THIS
 WAS APPLIED AS THE ENTIRE FLOOR.
 THIS IS TO BE CONFIRMED AND SUITE/UNIT NEEDS TO BE
 ADDED TO TITLEBLOCKS ONCE CONFIRMED.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS,
 PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION
 BELOW.
  