Plan Review Notes
Plan Review Notes For Permit 08020200
Permit Number 08020200
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-11 12:12:05*** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 FBC ADMIN SECTION 106.1.2, 106.5, FS 553.73
  
 2) NOTE: PLEASE SEE THE TABLE *C* LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ARE OVER THE MAXIMUM ALLOWANCES PER
 13-415.2.C.1.
 PLEASE VERY NEW AREAS OF WORK AND THE FIXTURE COUNT.
 THESE DO NOT COORDINATE. PLEASE SEE THE TABLE INDICATES
 A TOTAL OF 9 FIXTURES. ARE ALL THESE NEW? IF SO THE
 PLANS DO NOT SHOW ALL AS NEW. BASED ON NEW AND FIXTURES
 WHICH ARE *ASSUMED* AS EXISTING IT CAN NOT BE
 DETERMINED AT THIS TIME.
 PLEASE ALSO SEE THE TOTAL ALLOWANCE PER TABLE *C* IS
 1.0 AND THE CALCULATIONS SHOW AN ALLOWANCE OF 1.1 WHICH
 IS OVER.
 3) NOTE: PLEASE STATE MAXIMUM TIMES ON OS DEVICES.
 13-415.1.ABC.1.1, .1.2.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS,
 PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION
 BELOW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717