2008-02-11 11:56:01*** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE TABLE *C* LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ARE OVER THE MAXIMUM ALLOWANCES PER
 13-415.2.C.1.
 PLEASE VERY NEW AREAS OF WORK AND THE FIXTURE COUNT.
 THESE DO NOT COORDINATE. PLEASE SEE THE TABLE INDICATES
 A TOTAL OF 37 FIXTURES. ARE ALL THESE NEW? IF SO THE
 PLANS DO NOT SHOW ALL AS NEW. BASED ON NEW AND FIXTURES
 WHICH ARE *ASSUMED* AS EXISTING THE 37 IS LOWER THAN
 FIXTURES ON PLANS.
 PLEASE ALSO SEE THE TOTAL ALLOWANCE PER TABLE *C* IS
 1.0 AND THE CALCULATIONS SHOW A DESIGN OF 1.1 WHICH IS
 OVER.
  
 3) NOTE: PLEASE STATE MAXIMUM TIMES ON OS DEVICES.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE VERIFY IF EXISTING TRANSFORMER ON RISER
 IS BELOW CEILING.
 450.13B
  
  
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS,
 PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION
 BELOW.
  