| Plan Review Notes For Permit 08020195 |
| Permit Number |
08020195 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-09 11:25:03 | REVISION: CSST PIPING SIZED TO GASTITE TABLE 7-1. | | | | | | ****************PROVISO**************** | | | A} PER FBC MECHANICAL, SECTION *303.4 PROTECTION FROM | | | DAMAGE. APPLIANCES (WATER HEATER IN GARAGE) SHALL NOT | | | BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL | | | DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS. | | | | | | B} PER FBC FUEL GAS, SECTION *409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 3,750 CUBIC FEET REQUIRED. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|