| 2008-10-31 09:05:46 | |
| | ** DENIED REVISION** |
| | |
| | 1) NOTE: PLEASE SHOW AND DISPLAY ALL REVISIONS AS NOTED |
| | ON TITLE BLOCKS. FOR EXAMPLE THE LAST REVISION ON |
| | RECORD TO DATE FOR SHEET E500 IS REVISION #4, WHEREAS |
| | THE NEW REVISED SHEET CONTAINS REVISION #6. WHERE IS |
| | REVISION #5 LOCATED ON PLANS? NO CLOUDS OR TRIANGLES |
| | ARE SHOWN INDICATING THESE REVISIONS. THERE WAS A |
| | PREVIOUS REV #5 HOWEVER FOR OTHER SHEETS. |
| | PLEASE COORDINATE PLANS. |
| | FBC 106.1.1 |
| | FBC CHAPTER 13, NEC 220 |
| | |
| | 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE |
| | CALCULATIONS. AS THE FIXTURES HAVE BEEN REVISED TO |
| | INCREASE WATTAGES THE PREVIOUSLY SUBMITTED CALCULATIONS |
| | NO LONGER COORDINATE. |
| | PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |