| Plan Review Notes For Permit 08020160 |
| Permit Number |
08020160 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-10-27 15:34:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P202 REVISION 4 NOT APPROVED. VENT FROM FD-2 IS | | | SHOWN CONNECTING TO THE COLD WATER LINE. SECTION 608.1. | | | | | | 2. SHT P300 VENT FROM FD-2 DOES NOT REFLECT THE FLOOR | | | PLAN AS SHOWN ON SHT P202. THE FUTURE VENT SHOWN ON THE | | | FLOOR PLAN IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. | | | (SEE SPECIFIC NOTE #1 SHT P202). | | | | | | 3. A REVISION FOR SHT P201 IS REQUIRED TO REFLECT THE | | | CHANGE SHOWN ON THE SANITARY RISER AT COL. L-7, 12TH | | | FLOOR. SECTION 106.1.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|