| 2008-05-14 17:01:02 | AUDIT #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1 THROUGH 5: OK |
| | |
| | 6. THE SMOKE CONTROL SYSTEM FOR THIS BUILDING HAS BEEN |
| | TESTED, COMMISSIONED AND IS COMPLETE. A NEW RATIONAL |
| | ANALYSIS SUPPORTING THE DESIGN OF THE PROPOSED |
| | MODIFICATIONS WITHIN THIS TENANT SPACE AND A SEQUENCE |
| | OF OPERATIONS SHALL BE SUBMITTED PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | NOTE: ONCE CONSTRUCTION IS COMPLETE AND PRIOR TO A |
| | CERTIFICATE OF OCCUPANCY FOR THIS SPACE, THE BUILDING |
| | SMOKE CONTROL SYSTEM SHALL BE RE-TESTED AND |
| | RE-COMMISSIONED. THE EXTENT OF THE TESTING NECESSARY TO |
| | DEMONSTRATE THE FUNCTIONALITY OF NEW AND EXISTING |
| | PORTIONS OF THE SYSTEM MUST BE COORDINATED WITH THE |
| | CHIEF MECHANICAL INSPECTOR, FIRE MARSHAL AND |
| | COMMISSIONING AGENT. ANALYSIS AND TESTING SHALL BE DONE |
| | IN ACCORDANCE WITH FBCB SECTION 909. |
| | |
| | 7 THROUGH 11: OK |
| | |
| | 12. THE NOTICE TO BUILDING OFFICIAL AFFIDAVIT WHICH WAS |
| | PROVIDED IS A PHOTOCOPY. PLEASE PROVIDE ORIGINAL |
| | DOCUMENTATION WITH ORIGINAL SIGNATURES AND NOTARY |
| | STAMP. |
| | |
| | NEW: A PLAN REVIEW AFFIDAVIT FROM CAPRI ENGINEERING WAS |
| | NOT PROVIDED FOR THE FOLLOWING MECHANICAL PAGES WITH |
| | THIS SUBMITTAL: M300, M600, M700, M701, M702 SIGNED |
| | 3/11/08. |
| | |