| Date |
Text |
| 2008-05-20 12:08:18 | ** DENIED2ND AUDIT** |
| | |
| | ** PLEASE SEE SOME ITEMS STILL REMAIN FROM PREVIOUS |
| | AUDIT. |
| | |
| | 1) NOTE: PLEASE SEE AFFIDAVITS ARE NOW ONLY BEING |
| | SUBMITTED. PLEASE SEE THESE ARE BEING MADE OUT TO |
| | BALFOUR CONCORD. THE CONTRACTOR ON THIS PROJECT IS |
| | BALFOUR/BEATTY. |
| | PLEASE COORDINATE. |
| | PLEASE ALSO SEE NOTICE TO BUILDING OFFICIAL SUBMITTED |
| | WHICH IS IN FACT PHOTO-COPIES AND ARE NOT ORIGINAL. |
| | THESE CONTAIN STAMPS *REVIEWED FOR COMPLIANCE8 FROM THE |
| | PRIVATE PROVIDER. |
| | PLEASE ONLY INCLUDE ORIGINAL DOCUMENTS AND PLEASE BE |
| | SURE TO FILL OUT WITH THE CORRECT CONTRACTOR. |
| | |
| | 2) NOTE: PLEASE SUBMIT PLANS IN A NEAT AND ORDERLY |
| | FASHION WITH STAPLES SECURING ALL SHEETS TOGETHER. |
| | SEVERAL SHEETS IN THE BACK OF THE SETS WERE NOT SECURED |
| | TO THE REST OF THE SET. PLEASE ALSO DO NOT ATTACHED ALL |
| | OTHER DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. |
| | PLEASE SUBMIT THESE IN SOME SORT OF BINDER/FOLDER WHICH |
| | THESE DOCUMENTS MAY BE READILY GONE OVER. |
| | PLEASE KNOW THESE WERE DETACHED AND PLACED INTO |
| | SEPARATE CLIPS AT THIS TIME. |
| | PLEASE ALSO KNOW DUE TO SOME COMMENTS BELOW SOME |
| | DOCUMENTS MAY ALSO BE RETAINED BY THIS OFFICE. |
| | FBC 106.1.2, 106.1, 106.1.3, 106.5 FOR ADDITIONAL |
| | INFORMATION, SUBMITTING OF PLANS, RECORD DOCUMENTS. |
| | |
| | 3) NOTE: PLEASE SEE THE FLORIDA ENERGY EFFICIENCY CODE |
| | CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT. |
| | PLEASE SEE 13-400.3.A AS THE INCORRECT VERSION WAS |
| | SUBMITTED. THE VERSION SUBMITTED IS 3.0 WHEN THE CODE |
| | REQUIRES VERSION 2.5 WHEN USING FLA-COM PROGRAM. |
| | IN ANY CASE METHOD *A* MAY NOT BE USED AS THIS IS A |
| | TENANT SPACE BUILD OUT IN A BUILDING AND IS NOT A * |
| | WHOLE BUILDING*. PLEASE SEE THE DEFINITIONS IN THE FBC |
| | 13-400.0.A. PLEASE PROVIDE INFORMATION AND |
| | DOCUMENTATION EXPLAINING HOW METHOD *A* SUBMITTED IS |
| | BEING USED. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS WERE |
| | ALSO STAMPED AS BEING CODE COMPLIANT BY THE PRIVATE |
| | PROVIDER WHEN IN FACT THESE ARE NOT SIGNED, DATED OR |
| | SEALED BY ANY ENGINEER OF RECORD. PLEASE SEE 13-103.1 |
| | AS THIS SCOPE OF WORK IS REQUIRED TO BE DONE BY A |
| | LICENSED ENGINEER. PLEASE SEE THE SUBMITTED DOCUMENTS |
| | WERE SIGNED BY AN INDIVIDUAL WHICH DOES NOT LIST ANY |
| | LICENSE INFORMATION. IN FACT THE DOCUMENTS SUBMITTED |
| | CLEARLY SHOW A (PHOTO-COPIED SIGNATURE* FROM A |
| | *PREPARER* WHICH IS NOT LISTED AS A PE AND NOT AS ONE |
| | OF THE DESIGNERS OF RECORD. THIS IS THE SAME ON ALL |
| | THREE SETS SUBMITTED. |
| | WHEN SIGNING, DATING AND SEALING ANY DOCUMENTS AN |
| | ENGINEER MUST USE AN ORIGINAL SIGNATURE. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | 5) NOTE: ** PLEASE SEE THE LIGHTING CALCULATIONS ALSOO |
| | SUBMITTED ARE IN FACT PHOTO-METRIC LEVELS WHICH ARE NOT |
| | LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE KNOW THESE |
| | SHALL NOT BE USED IN LIEU OF REQUIRED CALCULATIONS. |
| | PLEASE KNOW THESE WERE GONE OVER IN MEETING HELD BEFORE |
| | RESUBMITTING PLANS HOWEVER THESE ARE STILL BEING |
| | SUBMITTED. |
| | ** FOR INFORMATION: |
| | PLEASE KNOW ANY DOCUMENTS SUBMITTED AND PART OF THE |
| | DESIGN OF A PROJECT BY THE ENGINEER SHALL BE SIGNED, |
| | DATED, SEALED CONTAINING TITLE BLOCKS ETC. |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS MEETING THE FLORIDA BUILDING CODE |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | THE LIGHTING DENSITIES LISTED ON SHEET E200 ARE NOT |
| | COMPLETE. PLEASE COMPLETE AS SEE LEVELS IN TABLES IN |
| | THE FBC. PLEASE BE SURE THE LIGHTING FIXTURE LEGEND |
| | COORDINATES WITH CALCULATIONS, NUMBERS OF FIXTURES, |
| | TYPES OF FIXTURES ETC TO COORDINATE CODE COMPLIANCE. |
| | ** PLEASE KNOW SOME LEVELS SHOWN IN THE SPACE BY SPACE |
| | EXCEED LEVELS IN 13-415.2.B |
| | |
| | 7) NOTE: PLEASE SEE MISSING MAXIMUM TIMES ON OVER RIDES |
| | AND OCCUPANCY SENSOR DEVICES. THE RESPONSE MENTIONS TO |
| | SEE E-100 AND E200 HOWEVER THE REVISED DEVICES, OVER |
| | RIDES AND OCCUPANCY SENSOR SWITCHES DO NOT INDICATE ANY |
| | TIMES. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SOME DEVICES ON PLANS ARE NOT ON SYMBOL |
| | LEGEND: FOR EXAMPLE PLEASE SEE READING ROOM AND OUTSIDE |
| | READING ROOM IN HALL AND SOME OTHER LOCATIONS WHICH |
| | SHOW A S IN A BOX HOWEVER NO OTHER DESIGNATION IS |
| | SHOWN. THERE IS NO S IN A SQUARE BOX ON SYMBOL LEGEND. |
| | WHICH DEVICE IS THIS? |
| | PLEASE COMPLETE. |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |