| Date |
Text |
| 2008-02-11 12:43:18 | AUDIT DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY MUNICIPAL CODE |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE |
| | NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN |
| | THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | |
| | 2. PER TABLE 403.1 2 DRINKING FOUNTAINS ARE REQUIRED. |
| | PLEASE INDICATE THE LOCATION OF EACH REQUIRED DRINKING |
| | FOUNTAIN. SECTION 106.1.1. |
| | |
| | 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | ANY FIXTURE. SECTION 11-4.22.3. |
| | |
| | 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | |
| | 6. SHT A1002 TOILET ROOMS 14-104, 14-105 & 14-310 STATE |
| | "CT-2 AT WET WALL, PT ALL OTHER WALLS". PER SECTION |
| | 1210.2 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE |
| | FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS |
| | NOT ADVERSELY AFFECTED BY MOISTURE. |
| | PAINTED SURFACES DOES NOT MEET THE REQUIREMENT FOR A |
| | "HARD SURFACE". |
| | |
| | 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | |
| | 8. SHT P001 INDICATE THE LISTING NUMBER FOR THE FLOOR |
| | AND WALL PENETRATIONS. SECTION 712.3.1.2. THROUGH |
| | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED.--ALSO THE FLOOR SLEEVE DETAIL INDICATES |
| | THAT THE SLEEVE SHALL BE 1" ABOVE THE FLOOR. WITH THE |
| | RISER CLAMP SITTING ON THE SLEEVE, PLEASE SUBMIT A |
| | DETAIL SHOWING HOW THE SLEEVE IS ATTACHED TO THE FLOOR |
| | AND INDICATE THE MATERIAL AND GUAGE FOR THE SLEEVE. |
| | SECTION 308.9. |
| | |
| | 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM |
| | RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE |
| | SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION |
| | 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED. |
| | SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING & |
| | RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE |
| | OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES |
| | INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR |
| | MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT |
| | SIZE. SECTION 607.3.2. |
| | |
| | 10. SHT P202 CONDENSATE SHALL NOT DRAIN TO THE SANITARY |
| | SYSTEM. MUNICIPAL CODE ARTICLE III SECTION |
| | 90-125(B)(5). CONDENSATE SHALL CONNECT TO THE |
| | CONDENSATE RISERS AND DRAIN SEPARATELY. |
| | |
| | 11. SHT P202 SPECIFIC NOTES #3 IS NOT FOUND ON THE |
| | FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 12. SHT P202 SHOWS 2 COLD WATER SUPPLIES TO THE SINK IN |
| | ROOM 14-130. HOT WATER IS REQUIRED PER SECTION 607.1. |
| | |
| | 13. SHT P202 WATER & VENT DROPS TO SINKS IN ROOMS |
| | 14-010, 14-100 & 14-106 AS WELL AS THE WATER & VENT |
| | DROPS BETWEEN THE TOILET ROOMS ARE SHOWN DROPING DOWN |
| | OUT OF THE WALL. PLEASE CLARIFY. |
| | |
| | 14. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN F-7 |
| | DOES NOT REFLECT THE FLOOR PLAN. THE EXTENTION OF THE |
| | FUTURE SANT IS NOT SHOWN ON THE FLOOR PLAN, THE FLOOR |
| | PLAN SHOWS OFFSETS IN THE 4" BRANCH LINE TO THE TOILET |
| | ROOM AND THE 1-1/2" LINE TO THE S-1 SINK. OFFSETS ARE |
| | NOT SHOWN ON THE RISER DIAGRAM. THE LINE TO THE S-1 |
| | SINK IS INDICATED AS 1-1/2" ON THE FLOOR PLAN, BUT 2" |
| | ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 15. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-7 |
| | DOES NOT REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE. |
| | THE HUB DRAIN FOR THE A/C CONDENSATE IS NOT APPROVED |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)(5). |
| | PLEASE DELETE. |
| | |
| | 16. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-5 |
| | DOES NOT REFLECT THE FLOOR PLAN. THE S-1 SINK AT THE |
| | SOUTH SIDE OF COLUMN SHOWS INDIVICUAL VENTS ON THE |
| | FLOOR PLAN, BUT SINGLE VENT ON THE RISER DIAGRAM.-- |
| | FLOOR PLAN SHOWS THE SANT. FOR THE SINK RUNNING SOUTH |
| | OF THE 3" STACK, BUT THE RISER DIAGRAM SHOWS THE PIPING |
| | RUNNING EAST THEN SOUTH.--THE 1ST RISER ON THE |
| | BRANCH LINE TO THE WEST, (FOR ROOMS 14-140 & 14-142), |
| | RISER IS SHOWN CONNECTING TO THE MAIN LINE RUNNING |
| | NORTH & SOUTH ON THE FLOOR PLAN, BUT ON THE WEST BRANCH |
| | LINE ON THE RISER DIAGRAM. OTHER RISERS ON THE WEST |
| | BRANCH LINE DO NOT REFLECT THE FLOOR PLAN.--THE 3" |
| | LINE CAPPED FOR THE FUTURE SHOWN ON THE FLOOR PLAN IS |
| | NOT SHOWN ON THE RISER DIAGRAM.--VENTING DOES NOT |
| | REFLECT THE FLOOR PLAN FOR THE FUTURE VENT AND THE SINK |
| | IN ROOM 14-161.--THE BRANCH LINES AT THE UPSTREAM |
| | END OF THE RISER DIAGRAM SHOW 4 RISERS TO THE WEST AND |
| | 1 RISER ON THE EAST BRANCH ON THE FLOOR PLAN, BUT SHOW |
| | 2 RISERS ON EACH BRANCH ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE AND SUBMIT THE RISER DIAGRAMS THAT REFLECT |
| | THE FLOOR PLAN. SECTIONS 106.1.1 & TABLE 710.1(2). |
| | |
| | 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL |
| | PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC. |
| | SECTIONS 106.3.5.1.3 & 604. |
| | |
| | 18. SUBMIT AN ISOMETRICCONDENSATE RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES TRAPS, VENTS, POINT OF |
| | CONNECTION TO THE CONDENSATE RISER ETC. SECTION |
| | 106.3.5.1.3. |
| | |
| | 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION |
| | TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE |
| | MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN |
| | OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, |
| | SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY |
| | WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT |
| | THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT, |
| | INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF |
| | FLORIDA STATUTE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |