| 2008-02-14 15:57:29 | *****DENIED***** |
| | |
| | |
| | 01.THE ASSIGNED SUITE NUMBER SHALL BE INCLUDED IN THE |
| | ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION |
| | CODE AS LISTED IN THE CODE NOTES ON SHEET G0201, NFPA |
| | 101- LIFE SAFETY CODE - 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 04.NO EXIT LIGHTS/DOORS SHOWN ON LIFE SAFETY PLAN |
| | (SHEET A0001) TO DETERMINE IF THE PATH OF TRAVEL IS TO |
| | THE EXIT(S). |
| | |
| | 05.ON SHEET A0401,EXIT LIGHTS DIRECT PERSON(S) TO |
| | THE CORRIDORS.WHERE DO PERSON(S) GO ONCE THEY'RE IN |
| | THE CORRIDOR?CORRELATE THIS SHEET WITH G0201, E200 |
| | |
| | 06.GENERAL SHEET NOTE # 5 INCOMPLETE AS SHOWN ON |
| | SHEETS A0501 AND A0502. |
| | |
| | 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO |
| | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON |
| | THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| | SHALL BE NO LESS THAN 3" IN HEIGHT. |
| | |
| | 08.DOOR(S) LEADING DIRECTLY TO THE CORRIDOR SHALL BE |
| | AN APPROVED, LISTED, AND LABELED FIRE DOOR & ASSEMBLY |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80. |
| | |
| | 09.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C. |
| | |
| | 10.PLEASE CLARIFY OR CORRELATE THE NUMBER OF CORRIDOR |
| | EMERGENCY LIGHTING FIXTURES.ON SHEET E200 AND SHEET |
| | E201 THER ARE15 DEVICES SHOWN, BUT 30 DEVICES ARE |
| | LISTED IN THE DESIGN CRITERIA LUMINAIRES USED |
| | INFORMATION DATA ON SHEET E201. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |