| 2008-11-06 13:56:08 | |
| | |
| | |
| | ** DENIED AUDIT OF REVISED PLANS. ** |
| | |
| | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL TO GO OVER. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED LIGHTING PERFORMANCE |
| | CALCULATIONS NEED TO BE UPDATED AS THE NUMBER OF |
| | FIXTURES, LOCATIONS ETC HAVE BEEN CHANGED. PLEASE ALSO |
| | SEE FOR EXAMPLE FIXTURE *R* WHICH DOES NOT INCLUDE |
| | ALLOWANCE. LED LIGHTING WILL STILL CONSUME ENERGY. |
| | 13-415.2.ABC.1.1,.1.2. |
| | |
| | ** AS A SIDE NOTE, PLEASE VERIFY ANY FIXTURE CHANGES |
| | WHICH MAY NEED TO BE UPDATED BASED ON ANY INCREASES OF |
| | WATTAGE PER FIXTURE. ( G)? |
| | THIS SAME FIXTURE WAS UPDATED ON OTHER PLANS FOR UPPER |
| | FLOOR WITH AN INCREASED WATTAGE. THIS IS ONLY NOTED. |
| | |
| | 2) NOTE: PLEASE SEE THE NEW CHILLER LOCATION IS MISSING |
| | REQUIRED GFI PER 210.63, 210.8B5 BAS EON CIRCUIT 30 IN |
| | PANEL PT121 THE SCHEDULE SEEMS TO INDICATE THE CIRCUIT |
| | TO THIS LOCATION HOWEVER BASED ON THE SITE PLAN THESE |
| | UNITS ARE IN TWO SEPARATE LOCATIONS. |
| | |
| | 3) NOTE: PLEASE ONLY SUBMIT PLANS WHICH ARE CURRENT AND |
| | BEING REVISED. |
| | |
| | 4) NOTE: PLEASE EXPLAIN HOW THE LOADS HAVE INCREASED ON |
| | PANEL LT 141 YET THE TOTAL LOAD CALCULATION ON E700 HAS |
| | NOT BEEN REVISED? |
| | NEC 220 |
| | FBC 106.1.1 FOR COORDINATION, CLARITY OF RECORD PLANS. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |